5.2.4 Check for available suction water
1. Open all supply, discharge, and pump isolation valves. Also open any other package
valves.
2. Close the bypass valve if it is installed in the piping by others.
3. Inspect the capillary tubing from the pump discharge to the suction header:
a) Open the petcocks that feed the tubing.
b) Make sure that the plastic tubing does not touch any metal surface. Protect the
tubing with insulation in order to prevent abrasion where it can possibly touch
metal.
4. Use the pump vent plugs and/or the vent cocks on the main PRV in order to prove that
there is available water from the suction.
5. Open a faucet in order to create a demand for water on the system pressure piping.
6. Observe the suction pressure and confirm that it is equal to or greater than the suction
pressure listed on the nameplate. System is designed for a specific suction pressure.
Deviation results in degraded system performance. Contact factory if suction pressure
varies from design specifications.
5.2.5 Start the package
1. Close the disconnect in order to apply power to the package.
2. Turn the panel switch to the local position.
3. Watch the screen as the boot-up progresses and note the serial number of the unit.
This is the password that you use for the setup menu.
4. If the unit starts, press the Stop button in order to stop the unit.
5.2.6 Check the pump rotation
1. Select the hand mode on the controller.
2. Enable the pump with the blinking green light.
Do not select any of the other pumps (no green light).
3. Press the start button and spin the first pump.
4. Immediately press the Stop button.
5. Observe the spinning shaft for rotation.
6. Repeat steps 1 through 5 for each pump.
7. If all pumps run backwards, reverse the two leads of the incoming power.
8. If only one of the pumps run backwards, reverse the two leads on the pump motors
that are incorrect.
5.2.7 Set the system operating pressure
1. Open a faucet or some other demand for water from the discharge of the package.
This can be anywhere in the building being served by the package.
2. In hand, run one pump.
5.2.8 Enter the setup menu
1. For each pump, confirm the settings entered for the pump motor data.
2. Review all settings for the compatibility with the installed application.
3. Make sure that these settings are in place:
Auto alt. prd. - 24 or 168 hours
Forced destage timer - 10 to 15 minutes
NFSD restart psi - Enter a value 5 to 10 psi less than the site-adjusted discharge
pressure
5 Commissioning, Startup, Operation, and Shutdown
TECHNOForce e-HV Mechanical Installation, Operation, and Maintenance Manual 19

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Xylem Bell & Gossett TECHNOForce e-HV Series and is the answer not in the manual?

Xylem Bell & Gossett TECHNOForce e-HV Series Specifications

General IconGeneral
BrandXylem
ModelBell & Gossett TECHNOForce e-HV Series
CategoryWater Pump
LanguageEnglish

Related product manuals