EasyManuals Logo

Xylem HYDROVAR HV 4.022 User Manual

Xylem HYDROVAR HV 4.022
104 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #26 background imageLoading...
Page #26 background image
26
9.2 EMC-electromagnetic compatibility
To ensure the electromagnetic compatibility the following points must be observed for
cable installation:
Earth / ground to ensure EMC
Protection earth
It is important to connect the HYDROVAR to PE, because of the earth leakage
current.
HF earth connection
Ground cables should be as short as possible and with lowest impedance.
Signal cables
Control and signal cables should be screened types to prevent disturbances from outside.
The screen should be only connected to ground on one end; to prevent ground loops. The
screen should be connected to HYDROVAR GND (use pre mounted cable-clips).
For small cable diameters the cable clips can be squeezed to ensure fixing.
To connect a screen with lowest impedance to ground, remove the insulation from the
signal cable and connect the screen to ground.
Signal cables must be installed separate from motor- and power- supply cables
If signal cables are installed in parallel to power supply cables (motor cables) for a longer
distance, the distance between these cables should be more than 200mm.
Do not cross power cables and control cables - if this is not possible, cross them only in an
angle of 90°.
Pre-mounted cable-clips

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Xylem HYDROVAR HV 4.022 and is the answer not in the manual?

Xylem HYDROVAR HV 4.022 Specifications

General IconGeneral
BrandXylem
ModelHYDROVAR HV 4.022
CategoryController
LanguageEnglish

Related product manuals