Page #71 background image
71
0285
0285 SKIPFRQ CTR
0,0 Hz
Skip frequency centre
Possible settings: f
min
- f
max
0286
0286 SKIPFRQ RNG
0,0 Hz
Skip frequency range
Possible settings: 0,0 – 5,0 Hz
0290
0290 CURR. LIMIT
OFF
Current limit functionality
Possible settings: OFF - ON
Possible settings: 10,0 - 100 %
Following parameters [0285] - [0291] are limited for power ratings starting from 5,5kW
(Size 2 and Size 3) with production date 05/08 and control board software V01.3 or above
Æ otherwise they are not visible and therefore not active.
0291
0291 CURR. LIMIT
100 %
Current limit
G