81
0570
0570 MSTPRIORITY
ON
MASTER priority
(for cascade serial / synchron only!)
Possible settings: ON - OFF
This parameter determines the alternation order when MASTER and BASIC Inverters are
used within one system. In such a case you have to select if either the MASTER or the BASIC
Inverters should be switched on first.
ON- all MASTER Inverters in the system are released (unless it is stopped by a failure or
manually) before the first BASIC Inverter gets released.
For example: Address 1-3.......MASTER Inverters
Address 4-8……BASIC Inverters
Switching order:
Adr 1
MASTER
Adr 2
MASTER
Adr 3
MASTER
Adr 4
BASIC
Adr 5
BASIC
Adr 6
BASIC
Adr 7
BASIC
Adr 8
BASIC
OFF- One MASTER (which is responsible for the controlling according the set value) is
running. With rising consumption all BASIC Inverters have to be released before any
other MASTER starts running.
Switching order:
Adr 1
MASTER
Adr 4
BASIC
Adr 5
BASIC
Adr 6
BASIC
Adr 7
BASIC
Adr 8
BASIC
Adr 2
MASTER
Adr 3
MASTER
S
G

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Xylem HYDROVAR HV 4.022 and is the answer not in the manual?

Xylem HYDROVAR HV 4.022 Specifications

General IconGeneral
BrandXylem
ModelHYDROVAR HV 4.022
CategoryController
LanguageEnglish

Related product manuals