en Original Instructions
24 e-SHE, e-SHS Additional Installation, Operation and Maintenance Instructions
NOTICE:
Only use single
-phase or three-phase motors with sizes and powers in compliance with
European standards.
NOTICE:
The mains voltage and frequency must match the specifications on the data plate.
Electrical connection of the motor
1. Open the terminal box cover.
2. Insert the power cable in the cable gland on the terminal board.
3. Unsheathe the conductors.
4. Referring to the figure below or to the wiring diagram inside the cover:
Connect the protection conductor (ground), making sure that it is longer than the phase
conductors
Connect the phase leads.
Position
Bolt size
Torque, Nm (lbf·in)
A
M4
1.2 (11)
M5
2.5 (22)
M6
4.0 (35)
M8
8.0 (71)
M10
15.0 (133)
B
M4
1.2 (11)
5. Tighten the cable gland.
6. Close the terminal box cover and tighten all the screws; see Tightening torques on page 31.
Motor without automatic reset thermal overload protection
If the motor is used with full load, then set the value to the nominal current value on the
data plate of the pump unit.
If the motor is used with partial load, then set the value of the operating current measured
with a current pincer.
For three-phase motors with star-delta starting system, set the thermal relay downstream of
the switching circuit at 58% of the rated or operating current.