User Constant Tables
5-53
* The CH1 output can be adjusted when the H4-02 or H4-03 setting is displayed in Quick, Advanced, or Verify mode while the motor is stopped.
The CH2 output can be adjusted when the H4-05 or H4-06 setting is displayed in Quick, Advanced, or Verify mode while the motor is stopped.
For analog output, the value equivalent to 100% of output value of monitored item is multiplied by the gain setting and the set bias is added.
MEMOBUS Communications: H5
User constants for MEMOBUS communications are shown in the following table.
H4-07
Analog out-
put 1 signal
level selec-
tion
Sets the signal output level
for multi-function output 1
(terminal FM)
0: 0 to +10 V output
1: 10 to 10 V output
0 or 1 0 No A A A A 423H 6-92
H4-08
Analog out-
put 2 signal
level selec-
tion
Sets the signal output level
for multi-function output 2
(terminal AM)
0: 0 to +10 V output
1: 10 to 10 V output
0 or 1 0 No A A A A 424H -
Con-
stant
Number
Name Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO
BUS
Regis-
ter
Page
V/f
V/f
with
PG
Open
Loop
Vec-
tor
Flux
Vec-
tor
H5-01
Slave
address
Set the Inverter's slave
address.
0 to 20
*1
1FH No A A A A 425H 6-98
H5-02
Communi-
cation speed
selection
Set the baud rate for
MEMOBUS communica-
tions of communications
connection terminals.
0: 1200 bps
1: 2400 bps
2: 4800 bps
3: 9600 bps
4: 19200 bps
0 to 4 3 No A A A A 426H 6-98
H5-03
Communi-
cation parity
selection
Set the parity for MEMO-
BUS communications of
communications connection
terminals.
0: No parity
1: Even parity
2: Odd parity
0 to 2 0 No A A A A 427H 6-98
H5-04
Stopping
method
after com-
munication
error
Set the stopping method for
communications errors.
0: Deceleration to stop
using deceleration time in
C1-02
1: Coast to stop
2: Emergency stop using
deceleration time in C1-
09
3: Continue operation
0 to 3 3 No A A A A 428H 6-98
Con-
stant
Number
Name Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO
BUS
Regis-
ter
Page
V/f
V/f
with
PG
Open
Loop
Vec-
tor
Flux
Vec-
tor