Wiring
Main and Control CircuitSection 4
Signal leads and feedback leads (PG) must be separated from control leads main circuit leads, and any other
power cables, to prevent erroneous operation caused by electrical noise.
Lead length should NOT EXCEED 164 feet (50 meters). Wire sizes should be determined considering the voltage
drop.
All AC relays, contactors and solenoids should have RC surge supressors installed across their coils.
All DC relays, contactors and solenoids should have diodes installed across their coils.
TO DRIVE
SIGNAL
TERMINALS
TO SHIELD
SHEATH
TERMINAL
(TERM. )
WRAP BOTH ENDS
OF SHEATH WITH
INSULATING TAPE
CRIMP
CONNECTION
SHIELD SHEATH
OUTER JACKET
DO NOT
CONNECT
TO
EXTERNAL
CIRCUIT
Figure 1-1. Shielded Sheath Termination