20
Wiring
Grounding Section 4
The Drive must be solidly grounded using the main circuit ground terminal .
If Drive is installed in a cabinet with other equipment, ground leads for all equipment should be connected to a
common low-impedance ground point within the cabinet.
The supply neutral should be connected to the ground point within the cabinet.
Select appropriate ground wire size from Table 1-1.
Make all ground wires as short as practical.
NEVER ground the Drive in common with welding machines, or other high power electrical equipment.
Where several Drives are used, ground each directly to the ground point (see Figure 1-2). DO NOT FORM A
LOOP WITH THE GROUND LEADS.
When connecting a motor to the Drive’s output terminals, include a separate ground wire. Attach ground wire
solidly to motor frame and to Drive’s ground terminal .
When using armored or shielded cable for connection between Drive and motor, solidly connect armor or shield
to motor frame, and to the Drive’s ground terminal .
Figure 1-2. Correct Ground Connection
CORRECT CORRECT NOT
ACCEPTABLE