11.6 C: Tuning
372 YASKAWA SIEPC71061753C GA500 Technical Manual
11.6 C: Tuning
C1: Accel & Decel Time
No.
(Hex.)
Name Description
Default
(Range)
Ref.
C1-01
(0200)
RUN
Acceleration Time 1
Sets the length of time to accelerate from zero to maximum output frequency.
10.0 s
(0.0 - 6000.0 s)
547
C1-02
(0201)
RUN
Deceleration Time 1
Sets the length of time to decelerate from maximum output frequency to zero.
10.0 s
(0.0 - 6000.0 s)
548
C1-03
(0202)
RUN
Acceleration Time 2
Sets the length of time to accelerate from zero to maximum output frequency.
10.0 s
(0.0 - 6000.0 s)
548
C1-04
(0203)
RUN
Deceleration Time 2
Sets the length of time to decelerate from maximum output frequency to zero.
10.0 s
(0.0 - 6000.0 s)
548
C1-05
(0204)
RUN
Acceleration Time 3
Sets the length of time to accelerate from zero to maximum output frequency.
10.0 s
(0.0 - 6000.0 s)
548
C1-06
(0205)
RUN
Deceleration Time 3
Sets the length of time to decelerate from maximum output frequency to zero.
10.0 s
(0.0 - 6000.0 s)
548
C1-07
(0206)
RUN
Acceleration Time 4
Sets the length of time to accelerate from zero to maximum output frequency.
10.0 s
(0.0 - 6000.0 s)
548
C1-08
(0207)
RUN
Deceleration Time 4
Sets the length of time to decelerate from maximum output frequency to zero.
10.0 s
(0.0 - 6000.0 s)
549
C1-09
(0208)
RUN
Fast Stop Time
Sets the length of time that the drive will decelerate to zero for a Fast Stop.
Note:
Decelerating too quickly can cause an ov [Overvoltage] fault that shuts off the
drive while the motor to coasts to a stop. Set a Fast Stop time in C1-09 that
prevents motor coasting and makes sure that the motor stops quickly and safely.
When L2-29 = 0 [Kinetic Energy Backup Method = Single Drive KEB Ride-Thru
1] and you do KEB Auto-Tuning, the drive will automatically set C1-09. If you
must not change the Fast Stop time, do not do KEB Tuning.
10.0 s
(0.0 - 6000.0 s)
549
C1-10
(0209)
Accel/Decel Time
Setting Units
Sets the setting units for C1-01 to C1-08 [Accel/Decel Times 1 to 4], C1-09 [Fast Stop
Time], L2-06 [Kinetic Energy Backup Decel Time], and L2-07 [Kinetic Energy Backup
Accel Time].
0 : 0.01 s (0.00 to 600.00 s)
1 : 0.1 s (0.0 to 6000.0 s)
1
(0, 1)
549
C1-11
(020A)
Accel/Decel Time
Switching Frequency
Sets the frequency at which the drive will automatically change acceleration and
deceleration times.
Determined by A1-02
(0.0 - 590.0 Hz)
549
C1-14
(0264)
RUN
Accel/Decel Rate
Frequency
Sets the base frequency used to calculate acceleration and deceleration rates.
0.0 Hz
(0.0 - 590.0 Hz)
550
C2: S-Curve Characteristics
No.
(Hex.)
Name Description
Default
(Range)
Ref.
C2-01
(020B)
S-Curve Time @ Start of
Accel
Sets the S-curve acceleration time at start.
Determined by A1-02
(0.00 - 10.00 s)
552
C2-02
(020C)
S-Curve Time @ End of
Accel
Sets the S-curve acceleration time at completion.
0.20 s
(0.00 - 10.00 s)
552
C2-03
(020D)
S-Curve Time @ Start of
Decel
Sets the S-curve deceleration time at start.
0.20 s
(0.00 - 10.00 s)
552
C2-04
(020E)
S-Curve Time @ End of
Decel
Sets the S-curve deceleration time at completion.
0.00 s
(0.00 - 10.00 s)
552
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV

Table of Contents

Other manuals for YASKAWA GA500 series

Related product manuals