EasyManua.ls Logo

YASKAWA GA500 series - Page 530

YASKAWA GA500 series
794 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
12.3 b: Application
530 YASKAWA SIEPC71061753C GA500 Technical Manual
Setting Parameter Description
b5-95 = 0 [EZ Sleep Wake-up Mode = Absolute] When the PID feedback is less than the value of b5-94 [EZ Sleep Wake-up Level] for longer than the time set
in b5-96 [EZ Sleep Wake-up Time], the drive restarts operation from sleep.
b5-95 = 1 [EZ Sleep Wake-up Mode = Setpoint Delta] The drive resumes operation from the sleep state when the PID feedback has dropped below the value
defined as the PID setpoint value minus b5-94 continuously for the time configured with b5-96.
Figure 12.32 EZ Sleep/Wake-up Operation: PID Output is Normal and b5-92 = 0.0 Hz
*1 The values of b5-94 and b5-95 set operation.
*2 In the example, b5-92 is at the default setting of 0.0 Hz. Parameter b5-91 is the EZ sleep level.
b5-01: PID Mode Setting
No.
(Hex.)
Name Description
Default
(Range)
b5-01
(01A5)
PID Mode Setting
Sets the type of PID control.
0
(0 - 8)
0 : Disabled
1 : Standard
Enables PID control. The drive does D control on the difference between the feedback value and the PID setpoint
output through U5-02 [PID Input].
2 : Standard (D on feedback)
Enables PID control. The drive does D control on the feedback output through U5-06 [PID FdbkDif PID Fdbk].
3 : Fref + PID Trim
Enables PID control. The drive adds the frequency reference to the PID output. The drive does D control on the
difference between the feedback value and the PID setpoint output through U5-02 [PID Input].
4 : Fref + PID Trim (D on feedback)
Enables PID control. The drive adds the frequency reference to the PID output. The drive does D control on the
feedback output through U5-06 [PID FdbkDif PID Fdbk].
5 : Same as 7series & prior, b5-01=1
6 : Same as 7series & prior, b5-01=2
7 : Same as 7series & prior, b5-01=3
8 : Same as 7series & prior, b5-01=4
Note:
Use settings 5 to 8 instead of settings 1 to 4 when the drive is a replacement for Varispeed F7.
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV

Table of Contents

Other manuals for YASKAWA GA500 series

Related product manuals