12.5 d: References
570 YASKAWA SIEPC71061753C GA500 Technical Manual
d1-08: Reference 8
No.
(Hex.)
Name Description
Default
(Range)
d1-08
(0287)
RUN
Reference 8
Sets the frequency reference in the units from o1-03 [Frequency Display Unit Selection].
0.00 Hz
(0.00 - 590.00 Hz)
Note:
The upper limit value changes when the E1-04 [Maximum Output Frequency] and d2-01 [Frequency Reference Upper Limit] values
change.
When A1-02 = 6 [Control Method Selection = AOLV/PM], the drive sets o1-03 = 1 [0.01% (100% = E1-04)].
This parameter sets the frequency reference of Multi-Step Speed 8.
d1-09: Reference 9
No.
(Hex.)
Name Description
Default
(Range)
d1-09
(0288)
RUN
Reference 9
Sets the frequency reference in the units from o1-03 [Frequency Display Unit Selection].
0.00 Hz
(0.00 - 590.00 Hz)
Note:
The upper limit value changes when the E1-04 [Maximum Output Frequency] and d2-01 [Frequency Reference Upper Limit] values
change.
When A1-02 = 6 [Control Method Selection = AOLV/PM], the drive sets o1-03 = 1 [0.01% (100% = E1-04)].
This parameter sets the frequency reference of Multi-Step Speed 9.
d1-10: Reference 10
No.
(Hex.)
Name Description
Default
(Range)
d1-10
(028B)
RUN
Reference 10
Sets the frequency reference in the units from o1-03 [Frequency Display Unit Selection].
0.00 Hz
(0.00 - 590.00 Hz)
Note:
The upper limit value changes when the E1-04 [Maximum Output Frequency] and d2-01 [Frequency Reference Upper Limit] values
change.
When A1-02 = 6 [Control Method Selection = AOLV/PM], the drive sets o1-03 = 1 [0.01% (100% = E1-04)].
This parameter sets the frequency reference of Multi-Step Speed 10.
d1-11: Reference 11
No.
(Hex.)
Name Description
Default
(Range)
d1-11
(028C)
RUN
Reference 11
Sets the frequency reference in the units from o1-03 [Frequency Display Unit Selection].
0.00 Hz
(0.00 - 590.00 Hz)
Note:
The upper limit value changes when the E1-04 [Maximum Output Frequency] and d2-01 [Frequency Reference Upper Limit] values
change.
When A1-02 = 6 [Control Method Selection = AOLV/PM], the drive sets o1-03 = 1 [0.01% (100% = E1-04)].
This parameter sets the frequency reference of Multi-Step Speed 11.
d1-12: Reference 12
No.
(Hex.)
Name Description
Default
(Range)
d1-12
(028D)
RUN
Reference 12
Sets the frequency reference in the units from o1-03 [Frequency Display Unit Selection].
0.00 Hz
(0.00 - 590.00 Hz)
Note:
The upper limit value changes when the E1-04 [Maximum Output Frequency] and d2-01 [Frequency Reference Upper Limit] values
change.
When A1-02 = 6 [Control Method Selection = AOLV/PM], the drive sets o1-03 = 1 [0.01% (100% = E1-04)].
This parameter sets the frequency reference of Multi-Step Speed 12.
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV