12.9 L: Protection Functions
714 YASKAWA SIEPC71061753C GA500 Technical Manual
L3-22: PM Stall Prevention Decel Time
No.
(Hex.)
Name Description
Default
(Range)
L3-22
(04F9)
PM Stall Prevention Decel
Time
Sets the momentary deceleration time that the drive will use when it tries to accelerate a PM
motor and detected motor stalls. This function is applicable when L3-01 = 1 [Stall Prevention
during Accel = Enabled].
0.0 s
(0.0 - 6000.0 s)
Set this parameter to 0.0 s to disable this function. The drive will decelerates in the deceleration time applicable at
the time when a motor stall occurs.
L3-23: Stall P Reduction at Constant HP
No.
(Hex.)
Name Description
Default
(Range)
L3-23
(04FD)
Stall P Reduction at
Constant HP
Sets the function to automatically decrease the Stall Prevention Level during Run for constant
output ranges.
0
(0, 1)
0 : Use L3-06 for Entire Speed Range
The drive uses the level set in L3-06 [Stall Prevent Level during Run] through the full speed range.
1 : Automatic Reduction @ CHP Region
The drive decreases the Stall Prevention level during run in the constant power range. The lower limit is 40% of
L3-06 value.
L3-24: Motor Accel Time @ Rated Torque
No.
(Hex.)
Name Description
Default
(Range)
L3-24
(046E)
Expert
Motor Accel Time @ Rated
Torque
Sets the motor acceleration time to reach the maximum frequency at the motor rated torque for
stopped single-drive motors.
Determined by o2-04, C6-
01, E2-11, and E5-01
(0.001 - 10.000 s)
Set one of these parameters to enable L3-20:
L2-29 = 1 [Kinetic Energy Backup Method = Single Drive KEB Ride-Thru 2]
L3-04 = 2 [Stall Prevention during Decel = Intelligent (Ignore Decel Ramp)]
L3-11 = 1 [Overvoltage Suppression Select = Enabled]
H1-xx = 7A or 7B [MFDI Function Select = KEB Ride-Thru 2 Activate (N.O./N.C.)]
Note:
When Auto-Tuning changes the value of E2-11 [Motor Rated Power (kW)], the drive will automatically set this parameter to the value
for a Yaskawa standard motor (4 poles). When you use a PM motor, the drive uses the value in E5-01 [PM Motor Code Selection] to
change L3-24.
L3-25: Load Inertia Ratio
No.
(Hex.)
Name Description
Default
(Range)
L3-25
(046F)
Expert
Load Inertia Ratio
Sets the ratio between motor inertia and machine inertia.
1.0
(0.1 - 1000.0)
Set one of these parameters to enable L3-20:
L2-29 = 1 [Kinetic Energy Backup Method = Single Drive KEB Ride-Thru 2]
L3-04 = 2 [Stall Prevention during Decel = Intelligent (Ignore Decel Ramp)]
L3-11 = 1 [Overvoltage Suppression Select = Enabled]
H1-xx = 7A or 7B [MFDI Function Select = KEB Ride-Thru 2 Activate (N.O./N.C.)]
Note:
If you set this value incorrectly when L2-29 = 1, H1-xx = 7A or 7B, or L3-11 = 1, it can cause large current ripples and ov
[Overvoltage], Uv1 [DC Bus Undervoltage], or oC [Overcurrent] faults.
KEB Tuning will automatically set this value.
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV