6 Overview of Keypad Components and Functions
20 YASKAWA TOEPC71061752B GA500 Drive Installation & Primary Operation
Symbol Name Function
J LED Display
Shows parameters, errors, and other data.
K
LO/RE Selection
Key
Switches drive control for the Run command and frequency reference between the
keypad (LOCAL) and an external source (REMOTE).
Note:
• The LOCAL/REMOTE Selection Key continuously stays enabled after the drive
stops in Drive Mode. If the application must not switch from REMOTE to LOCAL
because it will have a negative effect on system performance, set o2-01 = 0 [LO/
RE Key Function Selection = Disabled] to disable .
• The drive will not switch between LOCAL and REMOTE when it is receiving a
Run command from an external source.
L
REV LED Illuminated: The drive received a Reverse run command.
M
DWEZ LED Illuminated: The drive is In DriveWorksEZ operation.
N RJ-45 Connector
Connects to the drive. Use an RJ-45 8-pin straight through UTP CAT5e extension cable
to install the keypad in a different location than the drive.
WARNING
Sudden Movement Hazard. If you change the control source when b1-07 = 1 [LOCAL/
REMOTE Run Selection = Accept Existing RUN Command], the drive can start suddenly. Before you change the
control source, remove all personnel from the area around the drive, motor, and load. Sudden starts can cause
serious injury or death.