8 Electrical Installation
YASKAWA TOEPC71061752B GA500 Drive Installation & Primary Operation 65
Figure 8.17 Location of DIP Switch S1
Table 8.12 MFAI Terminal A2 Signal Settings
Terminal
Input
Signal
DIP Switch Settings Parameter
Switch Setting No. Signal Level
A2
Current
input
S1
I
(Default)
H3-09
2: 4 mA to 20 mA/0% to 100% (input impedance: 250
Ω)
3: 0 mA to 20 mA/0% to 100% (input impedance: 250
Ω)
Voltage
input
V
0: 0 V to 10 V/0% to 100% (with zero limit) (input
impedance: minimum 15 kΩ)
4: -10 V to +10 V/-100% to 100% (input impedance:
minimum 15 kΩ)
Note:
Use tweezers or a jig with a tip width of approximately 0.8 mm (0.03 in) to set DIP switches.
■ Set the Output Signal for the MFAO Terminal AM
Set the signal type for terminal AM to voltage or current output. Use jumper S5 and H4-07
[Terminal AM Signal Level Select] to set the signal type.