■ Control Circuit Wire Gauges and Tightening Torques
Use the tables in this section to select the correct wires. Use shielded wire to wire the control
circuit terminal block. Use crimp ferrules on the wire ends to make the wiring procedure easier
and more reliable.
Table 8.9 Control Circuit Wire Gauges and Tightening Torques
Terminal
Block
Terminal
Screw
Size
Tightening
Torque
N∙m (in∙lb)
Bare Wire Crimp Ferrule
Recomm.
Gauge
mm
2
(AWG)
Applicable
Gauge
mm
2
(AWG)
Recomm.
Gauge
mm
2
(AWG)
Applicable
Gauge
mm
2
(AWG)
TB1-1
PS, S1 - S7, SN,
SC, SP
M2
0.22 - 0.25
(1.95 - 2.21)
0.75
(18)
• Stranded
wire
0.25 - 1.0
(24 - 17)
• Solid wire
0.25 - 1.5
(24 - 16)
0.5
(20)
0.25 - 0.5
(24 - 20)
TB1-2
AM, AC, A1,
A2, +V, H1, H2,
HC
TB1-3
MP, RP, AC, D+,
D-, P1, C1, P2,
C2
TB2 MA, MB, MC M3
0.5 - 0.6
(4.4 - 5.3)
0.75
(18)
• Stranded
wire
0.25 - 1.5
(24 -16)
• Solid wire
0.25 - 1.5
(24 - 16)
0.5
(20)
0.25 - 1.0
(24 - 17)
Crimp Ferrules
Attach an insulated sleeve when you use crimp ferrules. Refer to Table 8.10 for the
recommended external dimensions and model numbers of crimp ferrules.
Use the CRIMPFOX 6, a crimping tool made by PHOENIX CONTACT.