6 Overview of Keypad Components and Functions
18 YASKAWA TOEPC71061752B GA500 Drive Installation & Primary Operation
6 Overview of Keypad Components and Functions
Figure 6.1 Keypad
Table 6.1 Keypad Components and Functions
Symbol Name Function
A
USB Terminal Pass-
through
Pass-through point to connect a USB cable to the drive to support the DriveWizard PC
tool and the DriveWizard Mobile App. Uses a USB cable (USB standard 2.0, type A -
mini-B) to connect the drive to a PC, Android smartphone, or tablet.
B
RUN Key
Starts the drive in LOCAL Mode.
Starts the operation in Auto-Tuning Mode.
Note:
Before you use the keypad to operate the motor, push on the keypad to set
the drive to LOCAL Mode.
C
STOP Key
Stops drive operation.
Note:
Uses a stop-priority circuit. Push to stop the motor. This will also apply
when a Run command (REMOTE Mode) is active at an external Run command
source. To disable priority, set o2-02 = 0 [STOP Key Function Selection =
Disabled].
D
LO/RE LED
Illuminated: The keypad controls the Run command (LOCAL Mode).
OFF: The control circuit terminal or serial transmission device controls the Run
command (REMOTE Mode).
Note:
• LOCAL: Use the keypad to operate the drive. Use the keypad to enter Run/Stop
commands and the frequency reference command.
• REMOTE: Use the control circuit terminal or serial transmission to operate the
drive. Use the frequency reference source entered in b1-01 and the Run command
source selected in b1-02.