5 Receiving
YASKAWA TOEPC71061752B GA500 Drive Installation & Primary Operation 17
Table 5.4 Three-Phase AC 400 V Class
Model
Heavy Duty Rating (HD)
[C6-01 = 0]
Normal Duty Rating (ND)
[C6-01 = 1]
(Default)
Maximum
Applicable Motor
Output
kW (HP)
Rated Output
Current
A
Maximum
Applicable Motor
Output
kW (HP)
Rated Output
Current
A
4001 0.2 (1/2) 1.2 0.4 (1/2) 1.2
4002 0.4 (3/4) 1.8 0.75 (1) 2.1
4004 0.75 (2) 3.4 1.5 (2) 4.1
4005 1.5 (3) 4.8 2.2 (3) 5.4
4007 2.2 (3) 5.6 3.0 (4) 7.1
4009 3.0 (4) 7.3 3.7 (5) 8.9
4012 3.7 (5) 9.2 5.5 (7.5) 11.9
4018 5.5 (10) 14.8 7.5 (10) 17.5
4023 7.5 (10) 18.0 11.0 (15) 23.4
4031 11.0 (15) 24.0 15.0 (20) 31.0
4038 15.0 (20) 31.0 18.5 (25) 38.0
4044 18.5 (25) 39.0 22.0 (30) 44.0
4060 22.0 (30) 45.0 30.0 (40) 60.0