9 Auto-Tuning
70 YASKAWA TOEPC71061752B GA500 Drive Installation & Primary Operation
Table 9.3 Auto-Tuning for PM Motors
Mode
Parameter
Settings
Application Conditions and Benefits
Applicable Control
Method
(A1-02 Setting)
OLV/PM
(5)
AOLV/PM
(6)
Manual Entry w/ Motor
Data Sheet
T2-01 = 0
• When the information from the motor
test report or motor nameplate is
available.
• Rotational/Stationary Auto-Tuning that
energizes the motor is not done.
Manually input the necessary motor
parameters.
x x
PM Stationary Auto-
Tuning
T2-01 = 1
• When the information from the motor
test report or motor nameplate is not
available.
Note:
With Stationary Auto-Tuning, the
energized drive stays stopped for
approximately 1 minute. During this
time, the drive automatically measures
the necessary motor parameters.
x x
PM Stationary Auto-
Tuning for Stator
Resistance
T2-01 = 2
• After Auto-Tuning, the wiring distance
between the drive and motor changed
by 50 m (164 ft) or more.
• When the motor output and drive
capacity are different.
x x
PM Motor Code Selection T2-01 = 4
• When the information from the motor
test report or motor nameplate is not
available.
• When you can decouple the motor and
load and the motor can rotate freely
while Auto-Tuning.
• The drive will automatically set the
values measured during Auto-Tuning
to the motor parameters.
x x
High Frequency Injection T2-01 = 5
• Automatically sets the control
parameters that are necessary to set n8-
35 = 1 [Initial Pole Detection Method
= High Frequency Injection] or n8-57
= 1 [HFI Overlap Selection =
Enabled].
• Applicable to IPM motors only.
• Do Auto-Tuning with the motor
connected to the drive.
Note:
When you set n8-35 = 1 or n8-57 = 1,
do High Frequency Injection Auto-
Tuning. Set the data on the motor
nameplate to the drive before you do
High Frequency Injection Auto-
Tuning. In High Frequency Injection
Auto-Tuning, the drive energizes the
stopped motor and automatically
adjusts the parameters.
x x