7.3 Program Table Operation
7.3.7 Program Table Operation Examples
7-36
Performing Registration
This example shows how to use the /RGRT signal during execution of a program step to
change to the specified speed and perform positioning for the specified distance.
Step 0 performs positioning for a travel distance (RDST) of 100,000 reference units when the /
RGRT signal turns ON.
The speed changes to 15,000,000 reference units/min (RSPD).
Step 1 performs positioning for a travel distance (RDST) of 100,000 reference units when the /
RGRT signal turns ON.
The speed changes to 15,000,000 reference units/min (RSPD).
The program table for this positioning is shown below.
Operating Procedure
Turn ON the /MODE 0/1 signal to change to mode 0.
Set the /SEL0 to /SEL4 signals to 0 to specify program step 0.
Turn ON the /START-STOP signal to start program table operation.
The /COIN signal turns OFF.
The /RGRT signal turns ON to perform registration operation.
The speed changes to the registration speed.
The /COIN turns ON when positioning is completed for the registration distance.
When execution of program step 1 starts, the /COIN signal turns OFF.
Operation Pattern and Related Signal Timing
*1. Do not change /SEL0 to /SEL7 for 4 ms after turning ON the /START-STOP signal.
*2. Pn635 = n.0 (Registration is started by changing the input signal from OFF (open) to ON (closed)): 20 μs
min.
Pn635 = n.1 (Registration is started by changing the input signal from ON (closed) to OFF (open)): 200 μs
min.
*3. The /RGRT signal is ignored during registration operation.
PGM-
STEP
POS SPD RDST RSPD ACC DEC POUT EVENT LOOP NEXT
0
I+200000
30000 100000 15000 400000 200000
NNNNNNNN
IT0 1 1
1
I-200000
30000 100000 15000 : :
: : : : : : : :
IT0 1 0
START-STOP
*1
/COIN
/MODE 0/1
*3
*2
/RGRT
/SEL0 to
/SEL4
*1
0
8 ms max.
Step 0
1 ms min.
Operation
Pattern
Speed
Time
Mode 0 (Program Table Operation)
Step 0 Step 1
1 ms min.