Installation Area
Do not install the drive to an area greater than pollution degree 2 (UL standard).
n
Ambient Temperature
IP00/Open Type Enclosure: -10 °C to +50 °C (14 °F to 122 °F)
IP20/NEMA 1, UL Type 1 Enclosure: -10 to +40 °C (14 °F to 104 °F)
Finless Type: IP20/IP00 Enclosure: -10 to +45 °C (14 °F to 113 °F)
n
Main Circuit Terminal Wiring
Yaskawa
recommends
using closed-loop crimp terminals on all drive models. Use only the tools recommended by the terminal
manufacturer for crimping. Refer to Closed-Loop Crimp Terminal Recommendations on page 104 for closed-loop crimp
terminal recommendations.
The wire gauges listed in the following tables are Yaskawa recommendations. Refer to local codes for proper wire gauge
selections.
Note:
The
mark indicates the terminals for protective ground connection.
Grounding impedance:
200 V: 100 Ω or less
400 V: 10 Ω or less
Wire Gauges and Tightening Torques
Refer to Main Circuit Wire Gauges and Tightening Torque on page 33.
n
Closed-Loop Crimp Terminal Recommendations
To maintain UL/cUL approval, UL Listed closed-loop crimp terminals are specifically required when wiring the drive main
circuit terminals on models 2o0068 to 2o0248 and 4o0052 to 4o0930. Use only the tools recommended by the terminal
manufacturer for crimping. Yaskawa recommends UL Listed crimp terminals made by JST and Tokyo DIP (or equivalent)
for the insulation cap. Table i.42 to Table i.44 match the wire gauges and terminal screw sizes with Yaskawa-recommended
crimp
terminals,
tools, and insulation caps. Refer to the appropriate Wire Gauge and Torque Specifications table for the wire
gauge and screw size for your drive model. Place orders with a Yaskawa representative or the Yaskawa sales department.
Drive Models 2o0028 to 2o0248 and 4o0011 to 4o0590
Table i.42 Closed-Loop Crimp Terminal Size
Drive Model
Wire Gauge
(AWG, kcmil)
Screw
Size
Crimp Terminal
Model Number
Tool
Insulation Cap
Model No.
Code
<1>
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
Machine No. Die Jaw
200 V Class
2o0028
10
M5
R5.5-5
YA-4
AD-900 TP-005 100-054-030
8
<2>
R8-5 AD-901 TP-008 100-054-032
2o0042
8
M6
R8-6
YA-4
AD-901 TP-008 100-065-184
6
<2>
R14-6 AD-902 TP-014 100-051-261
4 R22-6
YA-5 AD-953 TP-022 100-051-262
3 R22-6
2o0054
6
M6
R14-6
YA-5
AD-952 TP-014 100-051-261
4
<2>
R22-6 AD-953 TP-022 100-051-262
3
2o0068
4
<2>
M6 R22-6 YA-5 AD-953 TP-022 100-051-262
3
2o0081
6
<2>
M6
R14-6
YA-5
AD-952 TP-014 100-051-261
4
R22-6 AD-953 TP-022 100-051-262
3
i.9 Standards Compliance
104