Drive Models 2o0028 to 2o0248 and 4o0011 to 4o0590
+
+
-
+
+
+
-
+
+
S1
S2
S3
S4
S5
S6
S7
MP
DM
DM
RP
A1
A2
A3
0 V
AC
R
R
S
S-
IG
H1
H2
HC
2 k
S8
SC
0 V
0 V
AC
FM
AM
AC
E (G)
S1
S2
<16>
<10>
<17>
<15>
<11>
<13>
<10>
<6>
+24 V
+V
MA
M1
M2
MB
MC
Forward Run / Stop
Reverse Run / Stop
External fault
Fault reset
Multi-speed step 1
Multi-speed step 2
External Baseblock
Jog speed
Multi-function
digital inputs
(default setting)
Sink / Source mode
selection wire link
(default: Sink)
CN5-C
CN5-B
CN5-A
Option board
Pulse Train Input
(max 32 kHz)
Shield ground
terminal
Multi-function
analog/pulse
train inputs
Power supply +10.5 Vdc, max. 20 mA
Analog Input 1 (Frequency Reference Bias)
0 to +/-10Vdc (20 kΩ)
4 to 20 mA (250 Ω) / 0 to 20 mA (250 Ω)
Analog Input 2 (Frequency Reference Bias)
0 to +10Vdc (20 kΩ)
4 to 20 mA (250 Ω) / 0 to 20 mA (250 Ω)
Analog Input 3 (Aux. Frequency Reference)
0 to +/-10Vdc (20 kΩ)
4 to 20 mA (250 Ω) / 0 to 20 mA (250 Ω)
-V
Power supply, -10.5 Vdc, max. 20 mA
Safety
switch
MEMOBUS/Modbus comm.
RS-422/RS-485
max. 115.2 kbps
Safe Disable inputs
Wire
jumper
Open
Safety relay /
controller
Termination resistor
(120 , 1/2 W)
DIP
Switch S2
Fault relay output
250 Vac, max. 1 A
30 Vdc, max 1 A
(min. 5 Vdc, 10 mA)
Multi-function relay output (During Run)
250 Vac, max. 1 A
30 Vdc, max 1 A
(min. 5 Vdc, 10 mA)
Multi-function pulse train output
(Output frequency)
0 to 32 kHz (2.2 k )
Multi-function analog output 1
(Output frequency)
-10 to +10 Vdc (2mA)
or 4 to 20 mA
EDM (Safety Electronic Device Monitor)
shielded line
twisted-pair shielded line
main circuit terminal
control circuit terminal
M3
M4
Multi-function relay output (Zero Speed)
250 Vac, max. 1 A
30 Vdc, max 1 A
(min. 5 Vdc, 10 mA)
M5
M6
Multi-function relay output (Speed Agree 1)
250 Vac, max. 1 A
30 Vdc, max 1 A
(min. 5 Vdc, 10 mA)
SP
SN
<12>
AMFM
V
I
V
I
DIP Switch S1
A2 Volt/Curr. Sel
DIP Switch S4
A3 Analog/PTC
Input Sel
PTC
AI
Off
On
DIP Switch S2
Term. Res. On/Off
Jumper S3
H1, H2
Sink/Source Sel.
Jumper S5
AM/FM Volt./Curr.
Selection
Terminal board
jumpers and switches
FM
+
AM
<7>
<14>
<18>
<15>
Multi-function analog output 2
(Output current)
-10 to +10 Vdc (2mA)
or 4 to 20 mA
A+
A-
B-
Z-
B+
Z+
a+
a-
b+
b-
z+
z-
FE
IP
IG
TB1
SD
TB2
PG- X3
connectors
(option)
Slide Switch S6
DM+, DM-
N.C./N.O. Selection
<9>
<8>
<5>
ON
OFF
EMC filter
Switch
<19>
24
0
FE
24 V
0 V
24 V Control Power Supply
Unit Terminals
<20>
Drive
<4>
Control Circuit
p1
n1
<3>
Main Circuit
Terminals p1 and n1 are for
momentary power loss recovery
unit. Do not connect to AC power
supply.
B track monitor
A track monitor
M
U/T1
V/T2
W/T
U
V
W
3
Ground
PG
<2>
Cooling fan
M
FU
FV
FW
R/L1
S/L2
T/L3
ELCB (MCCB)
R
T
S
Three-phase
power supply
200 to 240 V
380 to 500 V
50/60 Hz
<1>
2MCCB
r1
s1
t1
MC
Wiring sequence should shut off
power to the drive when a fault
output is triggered.
MC
2MCCB
MB
ON
OFF
THRX
SA
1
2
TRX
MC
MA
TRX
Fault relay
contact
Braking resistor unit
Thermal relay trip contact
MC
MC
SA
SA
THRX
If running from a 400 V power supply,
a step-down transformer is needed to
reduce the voltage to 200 V.
N.C.
N.O.
Figure i.17 Drive Standard Connection Diagram (Example: Model 2o0028)
i.4 Electrical Installation
26
YASKAWA ELECTRIC TOEP C710636 04D U1000 Industrial MATRIX Drive Quick Start Guide