Main Circuit Wiring
This section describes the functions, specifications, and procedures required to safely and properly wire the main circuit in
the drive.
NOTICE: Do
not solder the ends of wire connections to the drive. Soldered wiring connections can loosen over time. Improper wiring practices
could result in drive malfunction due to loose terminal connections.
NOTICE: Do not switch the drive input to start or stop the motor. Frequently switching the drive on and off shortens the lifetime of the DC
bus charge circuit and the DC bus capacitors, and can cause premature drive failures. For the full performance life, refrain from switching
the drive on and off more than once every 30 minutes.
u
Main Circuit Terminal Functions
n
Drive Models 2o0028 to 2o0248 and 4o0011 to 4o0590
Table i.5 Main Circuit Terminal Functions
Voltage Class
Three-Phase 200 V
Class
Three-Phase 400 V
Class
Function Page
Drive Model
2o0028 to 2o0248 4o0011 to 4o0590
Terminal Type
R/L1, S/L2, T/L3 Main circuit power supply input Connects line power to the drive
26
U/T1, V/T2, W/T3 Drive output Connects to the motor
p1, n1 Momentary power loss recovery unit input
DC voltage terminals that connect to a
momentary power loss recovery unit
100 Ω or less 10 Ω or less Grounding terminal 40
n
Drive Models 4o0720 to 4o0930
Table i.6 Main Circuit Terminal Functions
Voltage Class
Three-Phase 400 V
Class
Function Page
Drive Model
4o0720 to 4o0930
Terminal Type
X, Y, Z
Main circuit power supply
input 1
Power supply input terminals that connect to the harmonic filter
module.
28
X1, Y1, Z1
Main circuit power supply
input 2
r1/ℓ11, 1/ℓ21, t1/ℓ31
Power supply voltage
detection input
Connects to the harmonic filter module to detects the power supply
voltage order and voltage levels.
U/T1, V/T2, W/T3 Drive output Connects to the motor
p1, n1
Momentary power loss
recovery unit input
DC voltage terminals that connect to a momentary power loss
recovery unit
p2, n2 DC voltage output DC voltage terminals that connect to the harmonic filter module
100 Ω or less Grounding terminal 40
n
Harmonic Filter Module
Table i.7 Harmonic Filter Module Main Circuit Terminal Functions
Terminal Type Function Page
R/L1, S/L2, T/L3
Main circuit power supply
input
Connects line power to the harmonic filter module
28
r1/ℓ11, 1/ℓ21, t1/ℓ31
Power supply voltage
detection input
Connects to drive models 4o0720 to 4o0930 to detect the power
supply voltage order and voltage levels
X, Y, Z Filter module output 1
Harmonic filter module output terminals that connect to drive models
4o0720 to 4o0930.
X1, Y1, Z1 Filter module output 2
p2, n2 DC voltage output
DC voltage terminals that connect to the drive models 4o0720 to
4o0930
100 Ω or less Grounding terminal 40
i.4 Electrical Installation