Characteristics Diagram
Single-phase, grounded at the end point
L1
N
Three-phase variable transformer without solidly grounded neutral
If EMC is a concern and the network is grounded symmetrically, install the SW screw to the ON position. Installing the SW
screw enables the internal EMC filter (Drives are shipped with the SW screw installed at the OFF position).
L1
L2
L3
Figure i.34 Symmetrical Grounded Network
n
EMC Filter Switch Location
A
B
E(G)
IG R+ R- S+ S-
S1 S2 S3 S4 S5 S6 S7 S8 SN SC SP
V+ AC A1 A2 A3 FM AM AC 24VRP AC
M1 M2 M3 M4
MD ME MF
MA MB MC
A – SW (ON) B – Screw (OFF)
Figure i.35 EMC Filter Switch Location
(Drive Models 2E0028, 2W0028, 4E0011 to 4E0034, and 4W0011 to 4W0034)
i.4 Electrical Installation
YASKAWA ELECTRIC TOEP C710636 04D U1000 Industrial MATRIX Drive Quick Start Guide