d1-04
d1-05
d1-06
d1-07
d1-17
d1-12
d1-13
d1-14
d1-15
d1-16
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
FWD (REV) Run/Stop
Multi-step Speed Ref. 2
Multi-step Speed Ref. 3
Jog Reference Selection
Time
Multi-step Speed Ref. 1
Multi-step Speed Ref. 4
Frequency
reference
d1-01
(A1)
d1-02
(A2)
d1-03
(A3)
Figure i.64 Preset Reference Timing Diagram
n
d2-01: Frequency Reference Upper Limit
Sets
the
maximum frequency reference as a percentage of the maximum output frequency. This limit applies to all frequency
references.
Even if the frequency reference is set to a higher value, the drive internal frequency reference will not exceed this value.
No. Parameter Name Setting Range Default
d2-01 Frequency Reference Upper Limit 0.0 to 110.0% 100.0%
n
d2-02: Frequency Reference Lower Limit
Sets
the
minimum frequency reference as a percentage of the maximum output frequency. This limit applies to all frequency
references.
If a lower reference than this value is entered, the drive will run at the limit set to d2-02. If the drive is started with a lower
reference than d2-02, it will accelerate up to d2-02.
No. Parameter Name Setting Range Default
d2-02 Frequency Reference Lower Limit 0.0 to 110.0% 0.0%
Internal frequency
reference
d2-01
Operating
range
Frequency Reference Upper Limit
Set frequency reference
Frequency Reference Lower Limit
d2-02
Figure i.65 Frequency Reference: Upper and Lower Limits
i.5 Start-Up Programming and Operation
YASKAWA ELECTRIC TOEP C710636 04D U1000 Industrial MATRIX Drive Quick Start Guide
75