YASKAWA U1000 - Alarm Codes

YASKAWA U1000
118 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
<1> Displayed as CPF00 when occurring at drive power up. When one of the faults occurs after successfully starting the drive, the display will show
CPF01.
<2> Displayed as CPF20 when occurring at drive power up. When one of the faults occurs after successfully starting the drive, the display will show
CPF21.
<3>
Fault histories are not kept when CPF00, CPF01, CPF06, CPF24, Fdv, oFA00, oFb00, oFC00, Uv1, Uv2, or Uv3 occur.
<4> This function prevents continuous operation in reverse when using high frequency injection (n8-57 = 1) in AOLV/PM (A1-02 = 6) with a motor
for which no motor code has been entered (it does not only prevent reverse operation). Set L8-93, L8-94, and L8-95 to low values within range of
erroneous detection to quickly detect undesirable reverse operation.
u
Alarm Detection
n
Alarm Codes
An
alarm is indicated by a code on the data display and the flashing ALM LED. The drive output is not necessarily switched
off.
To remove an alarm, trace and remove the cause, and reset the drive by pushing the Reset key on the operator or cycle the
power supply.
Refer to the Technical Manual for a complete list of causes and possible solutions.
Digital Operator Display Alarm Name
AEr
Station Address Setting Error (CC-Link, CANopen, MECHATROLINK)
Option card node address is outside of the acceptable setting range.
AUv
Power Supply Undervoltage
The input power supply voltage became equal to or lower than the Input Power Supply Undervoltage
Detection Level (L2-21).
200 V Class: Approximately 150 Vrms
400 V Class: Approximately 300 Vrms
bb
Baseblock
Drive output interrupted as indicated by an external baseblock signal.
bUS
Option Communication Error
The connection was lost after establishing initial communication.
Only detected when the run command frequency reference is assigned to an option card.
CALL
Serial Communication Transmission Error
Communication has not yet been established.
CE
MEMOBUS/Modbus Communication Error
Control data was not received for the CE detection time set to H5-09.
CrST Cannot Reset
CyC
MECHATROLINK Comm. Cycle Setting Error
Comm. Cycle Setting Error was detected.
dEv
Speed Deviation (for Control Mode with PG)
The deviation between the speed detection value for the pulse input and the speed reference after speed
agreement was
reached exceeded the setting value of F1-10 for the time set in F1-11 or longer when the
Operation Selection at Deviation was set to continue operation (F1-04 = 3).
dnE Drive Disabled
doH
Damping Resistor Overheat
The temperature of the built-in damping resistor exceeded the set value.
EF
Forward/Reverse Run Command Input Error
Both forward run and reverse run closed simultaneously for longer than 0.5 s.
EF0
Option Card External Fault
An external fault condition is present.
EF1
External Fault (input terminal S1)
External fault at multi-function input terminal S1.
EF2
External Fault (input terminal S2)
External fault at multi-function input terminal S2.
i.6 Troubleshooting
88
YASKAWA ELECTRIC TOEP C710636 04D U1000 Industrial MATRIX Drive Quick Start Guide