No. Name Description
E2-01 Motor Rated Current
Sets the motor nameplate full load current
in amps. Automatically set during
Auto-Tuning.
H1-01 to
H1-08
Multi-Function Digital
Input Terminal S1 to
S8 Function Selection
Selects the function of terminals S1 to S8.
H2-01
Multi-Function
Contact Output
(terminal M1-M2)
Sets the function for the relay output
M1-M2.
H2-02
Multi-Function
Contact Output 2
(terminal M3-M4)
Sets the function for the relay output
M3-M4.
H2-03
Terminal M5-M6
function selection
(relay)
Sets the function for the relay output
M5-M6
H2-06
Power Consumption
Output Unit Selection
0: 0.1 kWh units
<1>
1: 1 kWh units
2: 10 kWh units
3: 100 kWh units
4: 1000 kWh units
H2-07
MEMOBUS Register 1
Address Select
Sets the addresses of the MEMOBUS/
Modbus registers from which data will be
sent to contact outputs 62 and 162.
H2-08
MEMOBUS Register 1
Bit Select
Sets the bits for the MEMOBUS/Modbus
registers from which data will be sent to
contact outputs 62 and 162.
H2-09
MEMOBUS Register 2
Address Select
Sets the addresses of the MEMOBUS/
Modbus registers from which data will be
sent to contact outputs 63 and 163.
H2-10
MEMOBUS Register 2
Bit Select
Sets the bits for the MEMOBUS/Modbus
registers from which data will be sent to
contact outputs 63 and 163.
H3-01
Terminal A1 Signal
Level Selection
0: 0 to 10 V
1: -10 to 10 V
H3-02
Terminal A1 Function
Selection
Sets the function of terminal A1.
H3-03
Terminal A1 Gain
Setting
Sets the level of the input value selected in
H3-02 when 10 V is input at terminal A1.
H3-04
Terminal A1 Bias
Setting
Sets the level of the input value selected in
H3-02 when 0 V is input at terminal A1.
H3-05
Terminal A3 Signal
Level Selection
0: 0 to 10 V
1: -10 to 10 V
H3-06
Terminal A3 Function
Selection
Sets the function of terminal A3.
H3-07
Terminal A3 Gain
Setting
Sets the level of the input value selected in
H3-06 when 10 V is input at terminal A3.
H3-08
Terminal A3 Bias
Setting
Sets the level of the input value selected in
H3-06 when 0 V is input at terminal A3.
H3-09
Terminal A2 Signal
Level Selection
0: 0 to 10 V
1: -10 to 10 V
2: 4 to 20 mA
3: 0 to 20 mA
Note: Use DIP switch S1 to set
input terminal A2 for a
current or a voltage input
signal.
H3-10
Terminal A2 Function
Selection
Sets the function of terminal A2.
H3-11
Terminal A2 Gain
Setting
Sets the level of the input value selected in
H3-10 when 10 V (20 mA) is input at
terminal A2.
H3-12
Terminal A2 Bias
Setting
Sets the level of the input value selected in
H3-10 when 0 V (0 or 4 mA) is input at
terminal A2.
No. Name Description
H3-13
Analog Input Filter
Time Constant
Sets a primary delay filter time constant for
terminals A1, A2, and A3. Used for noise
filtering.
H3-14
Analog Input Terminal
Enable Selection
1: Terminal A1 only
2: Terminal A2 only
3: Terminals A1 and A2 only
4: Terminal A3 only
5: Terminals A1 and A3
6: Terminals A2 and A3
7: All terminals enabled
H3-16 Terminal A1 Offset
Adds an offset when the analog signal to
terminal A1 is at 0 V.
H3-17 Terminal A2 Offset
Adds an offset when the analog signal to
terminal A2 is at 0 V.
H3-18 Terminal A3 Offset
Adds an offset when the analog signal to
terminal A3 is at 0 V.
H4-01
Multi-Function Analog
Output Terminal FM
Monitor Selection
Selects the data to be output through multi-
function analog output terminal FM.
Set the desired monitor parameter to the
digits available in Uo-oo.
For example, enter “103” for U1-03.
H4-02
Multi-Function Analog
Output Terminal FM
Gain
Sets the signal level at terminal FM that is
equal to 100% of the selected monitor
value.
H4-03
Multi-Function Analog
Output Terminal FM
Bias
Sets the signal level at terminal FM that is
equal to 0% of the selected monitor value.
H4-04
Multi-Function Analog
Output Terminal AM
Monitor Selection
Selects the data to be output through multi-
function analog output terminal AM.
Set the desired monitor parameter to the
digits available in Uo-oo.
For example, enter “103” for U1-03.
H4-05
Multi-Function Analog
Output Terminal AM
Gain
Sets the signal level at terminal AM that is
equal to 100% of the selected monitor
value.
H4-06
Multi-Function Analog
Output Terminal AM
Bias
Sets the signal level at terminal AM that is
equal to 0% of the selected monitor value.
H4-07
Multi-Function Analog
Output Terminal FM
Signal Level Selection
0: 0 to 10 V
1: -10 to 10 V
2: 4 to 20mA
H4-08
Multi-Function Analog
Output Terminal AM
Signal Level Selection
0: 0 to 10 V
1: -10 to 10 V
2: 4 to 20 mA
H5-01 Drive Node Address
Selects drive station node number (address)
for MEMOBUS/Modbus
terminals R+, R-,
S+, S-. Cycle power for the setting to take
effect.
H5-02
Communication Speed
Selection
0: 1200 bps
1: 2400 bps
2: 4800 bps
3: 9600 bps
4: 19200 bps
5: 38400 bps
6: 57600 bps
7: 76800 bps
8: 115200 bps
Note: Cycle power
for the setting
to take effect.
H5-03
Communication Parity
Selection
0: No parity
1: Even parity
2: Odd parity
Note: Cycle power
for the setting
to take effect.
H5-04
Stopping Method After
Communication Error
(CE)
0: Ramp to stop
1: Coast to stop
2: Fast Stop
3: Alarm only
i.8 Parameter Table
96
YASKAWA ELECTRIC TOEP C710636 04D U1000 Industrial MATRIX Drive Quick Start Guide