User Constant Tables
5-27
Note The unit is set in o1-03 (frequency units of reference setting and monitor), default: 0.01 Hz.
* 1. The upper limit of the setting range depends on the upper limit set in E1-04.
* 2. When C6-01 = 1, the upper limit is 400.00.
* 3. When C6-01 = 0, the upper limit is 150.00.
Reference Limits: d2
User constants for frequency reference limits are shown in the following table.
d1-12
Frequency
reference 12
The frequency reference
when multi-step speed refer-
ences 1, 2, and 4 are ON for
multi-function inputs.
0.00 to
400.00
*1 *3
0.00
Hz
Yes A A A A 28DH -
d1-13
Frequency
reference 13
The frequency reference
when multi-step speed refer-
ences 3 and 4 are ON for
multi-function inputs.
0.00
Hz
Yes A A A A 28EH -
d1-14
Frequency
reference 14
The frequency reference
when multi-step speed refer-
ences 1, 3, and 4 are ON for
multi-function inputs.
0.00
Hz
Yes A A A A 28 FH -
d1-15
Frequency
reference 15
The frequency reference
when multi-step speed refer-
ences 2, 3, and 4 are ON for
multi-function inputs.
0.00 to
300.00
*1 *2
0.00
Hz
Yes A A A A 290H -
d1-16
Frequency
reference 16
The frequency reference
when multi-step speed refer-
ences 1, 2, 3, and 4 are ON
for multi-function inputs.
0.00
Hz
Yes A A A A 291H -
d1-17
Jog
frequency
reference
The frequency reference
when the jog frequency ref-
erence selection, FJOG com-
mand, or RJOG command is
ON.
6.00
Hz
Yes Q Q Q Q 292H
4-6
6-10
6-86
Con-
stant
Number
Name Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO
BUS
Regis-
ter
Page
V/f
V/f
with
PG
Open
Loop
Vec-
tor
Flux
Vec-
tor
d2-01
Frequency
reference
upper limit
Set the output frequency
upper limit as a percent, tak-
ing the max. output fre-
quency to be 100%.
0.0 to
110.0
100.0% No A A A A 289H
6-41
6-81
d2-02
Frequency
reference
lower limit
Sets the output frequency
lower limit as a percentage
of the maximum output fre-
quency.
0.0 to
110.0
0.0% No A A A A 28AH
6-41
6-81
d2-03
Master
speed refer-
ence lower
limit
Set the master speed refer-
ence lower limit as a percent,
taking the max. output fre-
quency to be 100%.
0.0 to
110.0
0.0% No A A A A 293H
6-41
6-81
Con-
stant
Number
Name Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO
BUS
Regis-
ter
Page
V/f
V/f
with
PG
Open
Loop
Vec-
tor
Flux
Vec-
tor

Table of Contents

Other manuals for YASKAWA Varispeed f7

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA Varispeed f7 and is the answer not in the manual?

YASKAWA Varispeed f7 Specifications

General IconGeneral
BrandYASKAWA
ModelVarispeed f7
CategoryInverter
LanguageEnglish

Related product manuals