EasyManuals Logo

YASKAWA Varispeed f7 User Manual

YASKAWA Varispeed f7
463 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #136 background imageLoading...
Page #136 background image
5-28
Jump Frequencies: d3
User constants for jump frequencies are shown in the following table.
* 1. When C6-01 = 1, the upper limit is 150.0.
* 2. When C6-01 = 0, the upper limit is 400.0.
Reference Frequency Hold: d4
User constants for the reference frequency hold function are shown in the following table.
Con-
stant
Number
Name Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO
BUS
Regis-
ter
Page
V/f
V/f
with
PG
Open
Loop
Vec-
tor
Flux
Vec-
tor
d3-01
Jump fre-
quency 1
Set the center values of the
jump frequencies in Hz.
This function is disabled by
setting the jump frequency to
0 Hz. Always ensure that the
following applies:
d3-01 d3-02 d3-03
Operation in the jump fre-
quency range is prohibited
but during acceleration and
deceleration, speed changes
smoothly without jump.
0.0 to
400.0
*1
0.0 Hz No A A A A 294H
4-20
6-38
d3-02
Jump fre-
quency 2
0.0 Hz No A A A A 295H
4-20
6-38
0.0 to
300.0
*2
d3-03
Jump fre-
quency 3
0.0 Hz No A A A A 296H
4-20
6-38
d3-04
Jump fre-
quency
width
Sets the jump frequency
bandwidth in Hz.
The jump frequency will be
the jump frequency ± d3-04.
0.0 to
20.0
1.0 Hz No A A A A 297H
4-20
6-38
Con-
stant
Number
Name Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO
BUS
Regis-
ter
Page
V/f
V/f
with
PG
Open
Loop
Vec-
tor
Flux
Vec-
tor
d4-01
Frequency
reference
hold func-
tion selec-
tion
Sets whether or not frequen-
cies on hold will be
recorded.
0: Disabled (when operation
is stopped or the power is
turned on again starts at
0.)
1: Enabled (when operation
is stopped or the power is
turned on again starts at
the previous hold
frequency.)
This function is available
when the multi-function
inputs “accel/decel Ramp
Hold” or “up/down” com-
mands are set.
0 or 1 0 No A A A A 298H 6-80

Table of Contents

Other manuals for YASKAWA Varispeed f7

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA Varispeed f7 and is the answer not in the manual?

YASKAWA Varispeed f7 Specifications

General IconGeneral
BrandYASKAWA
ModelVarispeed f7
CategoryInverter
LanguageEnglish

Related product manuals