User Constant Tables
5-37
Motor 2 Setup: E4
User constants for motor 2 are shown in the following table.
* 1. The factory settings depend on the Inverter capacity. The values for a 200 V Class Inverter of 0.4 kW are given.
* 2. The setting range is 10% to 200% of the Inverter's rated output current. The values for a 200 V Class Inverter of 0.4 kW is given.
* 3. If a multi-function input is set for motor 2 (H1- = 16), the setting range will depend upon the Inverter capacity. The value for a 200 V Class Inverter
of 0.4 kW is given.
Con-
stant
Number
Name Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO
BUS
Regis-
ter
Page
V/f
V/f
with
PG
Open
Loop
Vec-
tor
Flux
Vec-
tor
E4-01
Motor 2
rated cur-
rent
Sets the motor rated current
in 1 A units.
These set values will become
the reference values for
motor protection, torque lim-
its and torque control.
This constant is automati-
cally set during autotuning.
0.32
to 6.40
*2
1.90 A
*1
NoAAAA321H6-60
E4-02
Motor 2
rated slip
Sets the motor rated slip in
Hz units.
These set values will become
the reference values for slip
compensation.
This constant is automati-
cally set during autotuning.
0.00 to
20.00
2.90
Hz
*1
NoAAAA322H-
E4-03
Motor 2 no-
load current
Sets the motor no-load cur-
rent in 1 A units.
This constant is automati-
cally set during autotuning.
0.00 to
1.89
*3
1.20 A
*1
NoAAAA323H-
E4-04
Motor 2
number of
poles (num-
ber of poles)
Sets the number of motor
poles.
This constant is automati-
cally set during autotuning.
2 to 48 4 poles No No A No A 324H -
E4-05
Motor 2
line-to-line
resistance
Sets the motor phase-to-
phase resistance in Ω units.
This constant is automati-
cally set during autotuning.
0.000
to
65.000
9.842
Ω
*1
NoAAAA325H-
E4-06
Motor 2
leak induc-
tance
Sets the voltage drop due to
motor leakage inductance as
a percentage of the motor
rated voltage.
This constant is automati-
cally set during autotuning.
0.0 to
40.0
18.2%
*1
No No No A A 326H -
E4-07
Motor 2
rated capac-
ity
Set the rated output of the
motor in units of 0.01 kW.
This constant is automati-
cally set during autotuning.
0.00 to
650.00
0.40
kW
*1
NoAAAA327H-

Table of Contents

Other manuals for YASKAWA Varispeed f7

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA Varispeed f7 and is the answer not in the manual?

YASKAWA Varispeed f7 Specifications

General IconGeneral
BrandYASKAWA
ModelVarispeed f7
CategoryInverter
LanguageEnglish

Related product manuals