5-46
A
Acceleration/deceleration ramp hold (ON: Acceleration/deceleration
stopped, frequency on hold)
YesYesYesYes6-80
B OH2 alarm signal input (ON: OH2 will be displayed) Yes Yes Yes Yes -
C Multi-function analog input selection (ON: Enable) Yes Yes Yes Yes -
D
No V/f control with PG (ON: Speed feedback control disabled,) (normal V/f
control)
No Yes No No 6-136
E Speed control integral reset (ON: Integral control disabled) No Yes No Yes 6-136
F Not used (Set when a terminal is not used) - - - - -
10 Up command (Always set with the down command) Yes Yes Yes Yes 6-81
11 Down command (Always set with the up command) Yes Yes Yes Yes 6-81
12 FJOG command (ON: Forward run at jog frequency d1-17) Yes Yes Yes Yes 6-86
13 RJOG command (ON: Reverse run at jog frequency d1-17) Yes Yes Yes Yes 6-86
14 Fault reset (Reset when turned ON) Yes Yes Yes Yes 7-2
15
Emergency stop. (Normally open condition: Deceleration to stop in decelera-
tion time set in C1-09 when ON.)
YesYesYesYes6-24
16 Motor switch command (Motor 2 selection) Yes Yes Yes Yes -
17
Emergency stop (Normally closed condition: Deceleration to stop in deceler-
ation time set in C1-09 when OFF)
YesYesYesYes6-24
18
Timer function input (Functions are set in b4-01 and b4-02 and the timer
function outputs are set in H1- and H2-.)
YesYesYesYes
6-107
7-18
19 PID control disable (ON: PID control disabled) Yes Yes Yes Yes 6-111
1A Accel/Decel time 2 Yes Yes Yes Yes 6-26
1B
Constants write enable (ON: All constants can be written-in. OFF: All con-
stants other than frequency monitor are write protected.)
Yes Yes Yes Yes 6-154
1C
Trim control increase (ON: d4-02 frequency is added to analog frequency
reference.)
YesYesYesYes6-84
1D
Trim control decrease (ON: d4-02 frequency is subtracted from analog fre-
quency reference.)
YesYesYesYes6-84
1E Analog frequency reference sample/hold Yes Yes Yes Yes 6-85
20 to
2F
External fault (Desired settings possible)
Input mode: NO contact/NC contact, Detection mode: Normal/during opera-
tion
YesYesYesYes6-87
30
PID control integral reset (reset when reset command is input or when
stopped during PID control)
YesYesYesYes6-111
31 PID control integral hold (ON: Hold) Yes Yes Yes Yes 6-111
32 Multi-step speed reference 4 Yes Yes Yes Yes -
34 PID soft starter ON/OFF Yes Yes Yes Yes 6-111
35 PID input characteristics switch Yes Yes Yes Yes 6-111
60 DC injection braking command (ON: Performs DC injection braking) Yes Yes Yes Yes 6-23
61
External search command 1 (ON: Speed search from maximum output fre-
quency)
Yes No Yes No 6-69
62 External search command 2 (ON: Speed search from set frequency) Yes No Yes No 6-69
Set-
ting
Value
Function
Control Methods
Page
V/f
V/f
with
PG
Open
Loop
Vec-
tor
Flux
Vec-
tor