User Constant Tables
5-47
Multi-function Contact Outputs: H2
User constants for multi-function outputs are shown in the following tables.
Multi-function Contact Output Functions
63
Field weakening command (ON: Field weakening control set for d6-01 and
d6-02)
Yes Yes N o N o -
64 External speed search command 3 Yes Yes Yes Yes -
65 KEB (deceleration at momentary power loss) command (NC contact) Yes Yes Yes Yes -
66 KEB (deceleration at momentary power loss) command (NO contact) Yes Yes Yes Yes -
67
Communications test mode (“Pass” is displayed when the communication
test is passed.)
Yes Yes Yes Yes 6 - 10 6
68 High-slip braking (HSB) Yes Yes No No -
71 Speed/torque control change (ON: Torque control) No No No Yes
6-130
6-134
72 Zero-servo command (ON: Zero-servo) No No No Yes 6-144
77 Speed control (ASR) proportional gain switch (ON: C5-03) No No No Yes 6-136
78 Polarity reversing command for external torque reference No No No Yes 6-130
Con-
stant
Number
Name Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO
BUS
Regis-
ter
Page
V/f
V/f
with
PG
Open
Loop
Vec-
tor
Flux
Vec-
tor
H2-01
Terminal
M1-M2
function
selection
(contact)
Multi-function contact out-
put
0 to 37 0 No A A A A 40BH -
H2-02
Terminal P1
function
selection
(open col-
lector)
Multi-function contact out-
put 1
0 to 37 1 No A A A A 40CH -
H2-03
Terminal P2
function
selection
(open col-
lector)
Multi-function contact out-
put 2
0 to 37 2 No A A A A 40DH -
Set-
ting
Value
Function
Control Methods
Page
V/f
V/f
with
PG
Open
Loop
Vec-
tor
Flux
Vec-
tor
0 During run (ON: Run Command is ON or voltage is being output) Yes Yes Yes Yes 6-88
1 Zero-speed Yes Yes Yes Yes 6-88
2 Frequency agree 1 (L4-02 used.) Yes Yes Yes Yes 6-54
3
Desired frequency agree 1 (ON: Output frequency = ±L4-01, L4-02 used and
during frequency agree)
Yes Yes Yes Yes 6-54
Set-
ting
Value
Function
Control Methods
Page
V/f
V/f
with
PG
Open
Loop
Vec-
tor
Flux
Vec-
tor