5-48
4
Frequency (FOUT) detection 1 (ON: +L4-01 ≥ output frequency ≥ -L4-01,
L4-02 used)
YesYesYesYes6-54
5
Frequency (FOUT) detection 2 (ON: Output frequency ≥ +L4-01 or output
frequency ≤ -L4-01, L4-02 used)
YesYesYesYes6-54
6
Inverter operation ready
READY: After initialization, no faults
YesYesYesYes -
7 During DC bus undervoltage (UV) detection Yes Yes Yes Yes -
8 During baseblock (ON: during baseblock) Yes Yes Yes Yes -
9 Frequency reference selection (ON: Frequency reference from Operator) Yes Yes Yes Yes -
A Run Command selection status (ON: Run Command from Operator) Yes Yes Yes Yes -
B
Overtorque/undertorque detection 1 NO (NO contact: Overtorque/under-
torque detection at ON)
YesYesYesYes6-57
C Loss of frequency reference (Effective when 1 is set for L4-05) Yes Yes Yes Yes 6-74
D Braking resistor fault (ON: Resistor overheat or braking transistor fault) Yes Yes Yes Yes 6-76
E
Fault (ON: Digital Operator communications error or fault other than CPF00
and CPF01 has occurred.)
YesYesYesYes -
F Not used. (Set when the terminals are not used.) - - - - -
10 Minor fault (ON: Alarm displayed) Yes Yes Yes Yes -
11 Fault reset command active Yes Yes Yes Yes -
12 Timer function output Yes Yes Yes Yes 6-107
13 Frequency agree 2 (L4-04 used) Yes Yes Yes Yes 6-54
14
Desired frequency agree 2 (ON: Output frequency = L4-03, L4-04 used, and
during frequency agree)
YesYesYesYes6-54
15 Frequency detection 3 (ON: Output frequency ≤ L4-03, L4-04 used) Yes Yes Yes Yes 6-54
16 Frequency detection 4 (ON: Output frequency ≥ L4-03, L4-04 used) Yes Yes Yes Yes 6-54
17
Overtorque/undertorque detection 1 NC (NC Contact: Torque detection at
OFF)
YesYesYesYes6-57
18
Overtorque/undertorque detection 2 NO (NO Contact: Torque detection at
ON)
YesYesYesYes6-57
19
Overtorque/undertorque detection 2 NC (NC Contact: Torque detection at
OFF)
YesYesYesYes6-57
1A During reverse run (ON: During reverse run) Yes Yes Yes Yes -
1B During baseblock 2 (OFF: During baseblock) Yes Yes Yes Yes -
1C Motor selection (Motor 2 selected) Yes Yes Yes Yes -
1D During regeneration (ON: During regeneration) No No No Ye s -
1E Restart enabled (ON: Restart enabled) Yes Yes Yes Yes 6-74
1F
Motor overload (OL1, including OH3) pre-alarm (ON: 90% or more of the
detection level)
YesYesYesYes
6-61
6-89
20 Inverter overheat (OH) pre-alarm (ON: Temperature exceeds L8-02 setting) Yes Yes Yes Yes 6-89
30 During torque limit (current limit) (ON: During torque limit) No No Yes Yes -
31 During speed limit (ON: During speed limit) No No No Yes 6-89