User Constant Tables
5-53
* The CH1 output can be adjusted when the H4-02 or H4-03 setting is displayed in Quick, Advanced, or Verify mode while the motor is stopped.
The CH2 output can be adjusted when the H4-05 or H4-06 setting is displayed in Quick, Advanced, or Verify mode while the motor is stopped.
For analog output, the value equivalent to 100% of output value of monitored item is multiplied by the gain setting and the set bias is added.
MEMOBUS Communications: H5
User constants for MEMOBUS communications are shown in the following table.
H4-06
Bias (termi-
nal AM)
Sets the multi-function ana-
log output 2 voltage level
bias.
Sets output characteristic up/
down parallel movement as a
percentage of 10 V.
The maximum output from
the terminal is 10 V.
A meter calibration function
is available.
*
-10.0 to
+10.0
0.0% Yes A A A A 422H 6-91
H4-07
Analog out-
put 1 signal
level selec-
tion
Sets the signal output level
for multi-function output 1
(terminal FM)
0: 0 to +10 V output
1: 0 to ±10 V output
0 or 1 0 No A A A A 423H 6-91
H4-08
Analog out-
put 2 signal
level selec-
tion
Sets the signal output level
for multi-function output 2
(terminal AM)
0: 0 to +10 V output
1: 0 to ±10 V output
0 or 1 0 No A A A A 424H -
Con-
stant
Number
Name Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO
BUS
Regis-
ter
Page
V/f
V/f
with
PG
Open
Loop
Vec-
tor
Flux
Vec-
tor
H5-01
Slave
address
Set the Inverter's slave
address.
0 to 20
*
1FH No A A A A 425H 6-97
H5-02
Communi-
cation speed
selection
Set the baud rate for 6CN
MEMOBUS communica-
tions.
0: 1200 bps
1: 2400 bps
2: 4800 bps
3: 9600 bps
4: 19200 bps
0 to 4 3 No A A A A 426H 6-97
H5-03
Communi-
cation parity
selection
Set the parity for 6CN
MEMOBUS communica-
tions.
0: No parity
1: Even parity
2: Odd parity
0 to 2 0 No A A A A 427H 6-97
Con-
stant
Number
Name Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO
BUS
Regis-
ter
Page
V/f
V/f
with
PG
Open
Loop
Vec-
tor
Flux
Vec-
tor

Table of Contents

Other manuals for YASKAWA Varispeed f7

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA Varispeed f7 and is the answer not in the manual?

YASKAWA Varispeed f7 Specifications

General IconGeneral
BrandYASKAWA
ModelVarispeed f7
CategoryInverter
LanguageEnglish

Related product manuals