* Set H5-01 to 0 to disable Inverter responses to MEMOBUS communications.
Pulse Train I/O: H6
User constants for pulse I/O are shown in the following table.
H5-04
Stopping
method
after com-
munication
error
Set the stopping method for
communications errors.
0: Deceleration to stop
using deceleration time in
C1-02
1: Coast to stop
2: Emergency stop using
deceleration time in C1-
09
3: Continue operation
0 to 3 3 No A A A A 428H 6-97
H5-05
Communi-
cation error
detection
selection
Set whether or not a commu-
nications timeout is to be
detected as a communica-
tions error.
0: Do not detect.
1: Detect
0 or 1 1 No A A A A 429H 6-97
H5-06
Send wait
time
Set the time from the
Inverter receiving data to
when the Inverter starts to
send.
5 to 65 5 ms No A A A A 42AH 6-97
H5-07
RTS con-
trol ON/
OFF
Select to enable or disable
RTS control.
0: Disabled (RTS is always
ON)
1: Enabled (RTS turns ON
only when sending)
0 or 1 1 No A A A A 42BH 6-97
Con-
stant
Number
Name Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO
BUS
Regis-
ter
Page
V/f
V/f
with
PG
Open
Loop
Vec-
tor
Flux
Vec-
tor
H6-01
Pulse train
input func-
tion selec-
tion
0: Frequency reference
1: PID feedback value
2: PID target value
0 to 2 0 No A A A A 42CH
6-6
6-40
6-110
H6-02
Pulse train
input scal-
ing
Set the number of pulses in
hertz, taking the reference to
be 100%.
1000 to
32000
1440
Hz
Yes A A A A 42DH
6-6
6-40
H6-03
Pulse train
input gain
Set the input gain level as a
percent when the pulse train
set in H6-02 is input.
0.0 to
1000.0
100.0% Yes A A A A 42EH 6-40
H6-04
Pulse train
input bias
Set the input bias when the
pulse train is 0.
-100.0
to
100.0
0.0% Yes A A A A 42FH 6-40
H6-05
Pulse train
input filter
time
Set the pulse train input pri-
mary delay filter time con-
stant in seconds.
0.00 to
2.00
0.10 s Yes A A A A 430H 6-40
Con-
stant
Number
Name Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO
BUS
Regis-
ter
Page
V/f
V/f
with
PG
Open
Loop
Vec-
tor
Flux
Vec-
tor

Table of Contents

Other manuals for YASKAWA Varispeed f7