6-18
* 0 or 1 for flux vector control.
b2-02
DC injection
braking cur-
rent
Sets the DC injection braking
current as a percentage of the
Inverter rated current.
The DC injection braking cur-
rent in flux control is affected by
any change to the setting of E2-
03.
0 to
100
50% No A A A No 18AH
b2-03
DC injection
braking time
at start
Used to set the time to perform
DC injection braking at start in
units of 1 second.
Used to stop coasting motor and
restart it. When the set value is
0, DC injection braking at start
is not performed.
0.00
to
10.00
0.00 s No A A A A 18BH
b2-04
DC injection
braking time
at stop
Used to set the time to perform
DC injection braking at stop
(zero-speed control in flux vec-
tor control) in units of 1 second.
Used to prevent coasting after
the Stop Command is input.
When the set value is 0.00, DC
injection braking at stop is not
performed.
0.00
to
10.00
0.50 s No A A A A 18CH
Con-
stant
Number
Name Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO
BUS
Regis-
ter
V/f
V/f
with
PG
Open
Loop
Vec-
tor
Flux
Vec-
tor