2-10
* The wire thickness is set for copper wires at 75°C.
F7A4185
R/L1, S/L2, T/L3 M16 78.4 to 98
100 to 325
(4/0 to 600)
150 × 2P
(300 × 2P)
Power cables,
e.g., 600 V vinyl
power cables
U/T1, V/T2, W/T3, R1/L11, S1/L21, T1/L31 M16 78.4 to 98
100 to 325
(4/0 to 600)
125 × 2P
(250 × 2P)
, 1
M16 78.4 to 98
100 to 325
(4/0 to 600)
325 × 2P
(600 × 2P)
3
M16 78.4 to 98
100 to 325
(4/0 to 600)
-
M16 78.4 to 98
100 to 325
(4/0 to 600)
100 × 2P
(3/0 × 2P)
r/ 1, 200/
2
200, 400/
2
400
M4 1.3 to 1.4
0.5 to 5.5
(20 to 10)
1.25
(16)
F7A4220
R/L1, S/L2, T/L3 M16 78.4 to 98
100 to 325
(4/0 to 600)
250 × 2P
(500 × 2P)
U/T1, V/T2, W/T3, R1/L11, S1/L21, T1/L31 M16 78.4 to 98
100 to 325
(4/0 to 600)
200 × 2P
(400 × 2P)
, 1
M16 78.4 to 98
100 to 325
(4/0 to 600)
125 × 4P
(250 × 4P)
3
M16 78.4 to 98
100 to 325
(4/0 to 600)
-
M16 78.4to 98
100 to 325
(4/0 to 600)
125 × 2P
(250 × 2P)
r/ 1, 200/
2
200, 400/
2
400
M4 1.3 to 1.4
0.5 to 5.5
(20 to 10)
1.25
(16)
F7A4300
R/L1, S/L2, T/L3 M16 78.4 to 98
100 to 325
(4/0 to 600)
125 × 4P
(250 × 4P)
R1/L11, S1/L21, T1/L31 M16 78.4 to 98
100 to 325
(4/0 to 600)
125 × 2P
(250 × 2P)
U/T1, V/T2, W/T3 M16 78.4 to 98
100 to 325
(4/0 to 600)
125 × 4P
(4/0 × 4P)
, 1
M16 78.4 to 98
100 to 325
(4/0 to 600)
200 × 4P
(400 × 4P)
3
M16 78.4 to 98
100 to 325
(4/0 to 600)
-
M16 78.4 to 98
100 to 325
(4/0 to 600)
125 × 2P
(250 × 2P)
r/ 1, 200/
2
200, 400/
2
400
M4 1.3 to 1.4
0.5 to 5.5
(20 to 10)
1.25
(16)
Table 2.2 400 V Class Wire Sizes (Continued)
Inverter
Model
CIMR-
Terminal Symbol
Termi-
nal
Screws
Tightening
Torque
(N•m)
Possible
Wire Sizes
mm
2
(AWG)
Recom-
mended
Wire Size
mm
2
(AWG)
Wire Type