10-34
H1-04 Terminal S6 function selection
4 (3)
*12
H6-03 Pulse train input gain 100.0
H1-05 Terminal S7 function selection
6 (4)
*12
H6-04 Pulse train input bias 0.0
H1-06 Terminal S8 function selection
8 (6)
*12
H6-05 Pulse train input filter time 0.10
H2-01
Terminal M1-M2 function selec-
tion (contact)
0 H6-06 Pulse train monitor selection 2
H2-02
Terminal P1 function selection
(open collector)
1 H6-07 Pulse train monitor scaling 1440
H2-03
Terminal P2 function selection
(open collector)
2 L1-01 Motor protection selection 1
H3-01
Signal level selection (terminal
A1)
0 L1-02 Motor protection time constant 1.0
H3-02 Gain (terminal A1) 100.0 L1-03
Alarm operation selection during
motor overheating
3
H3-03 Bias (terminal A1) 0.0 L1-04
Motor overheating operation selec-
tion
1
H3-04
Signal level selection (terminal
A3)
0 L1-05
Motor temperature input filter time
constant
0.20
H3-05
Multi-function analog input (termi-
nal A3) function selection
1F L2-01 Momentary power loss detection 0
H3-06 Gain (terminal A3) 100.0 L2-02
Momentary power loss ridethru
time
0.1
*6
H3-07 Bias (terminal A3) 0.0 L2-03 Min. baseblock time
0.2
*6
H3-08
Signal level selection (terminal A2)
2 L2-04 Voltage recovery time
0.3
*6
H3-09
Multi-function analog input (termi-
nal A2) function selection
0 L2-05 Undervoltage detection level
190
*9
H3-10 Gain (terminal A2) 100.0 L2-06 KEB deceleration time 0.0
H3-11 Bias (terminal A2) 0.0 L2-07 Momentary recovery time
0.0
*13
H3-12 Analog input filter time constant
0.00 L2-08
Frequency reduction gain at KEB
start
100
0.03 L3-01
Stall prevention selection during
accel
1
H3-13 Terminal A1/A2 switching 0
L3-02 Stall prevention level during accel
120
*14
H4-01 Monitor selection (terminal FM) 2
150
*14
H4-02 Gain (terminal FM) 1.00 L3-03 Stall prevention limit during accel 50
H4-03 Bias (terminal FM) 0.0 L3-04
Stall prevention selection during
decel
1
H4-04 Monitor selection (terminal AM) 3 L3-05
Stall prevention selection during
running
1
H4-05 Gain (terminal AM) 0.50
L3-06
Stall prevention level during run-
ning
120
*14
H4-06 Bias (terminal AM) 0.0
150
*14
H4-07
Analog output 1 signal level selec-
tion
0
L3-11 Overvoltage inhibit selection 0
L3-12 Overvoltage inhibit voltage level
380V
*9
H4-08
Analog output 2 signal level selec-
tion
0 L4-01 Speed agreement detection level 0.0
H5-01 Slave address 1F L4-02 Speed agreement detection width 2.0
H5-02 Communication speed selection 3 L4-03
Speed agreement detection level
(+/-)
0.0
H5-03 Communication parity selection 0 L4-04
Speed agreement detection width
(+/-)
2.0
H5-04
Stopping method after communi-
cation error
3 L4-05
Operation when frequency refer-
ence is missing
0
H5-05
Communication error detection
selection
1 L5-01 Number of auto restart attempts 0
H5-06 Send wait time 5 L5-02 Auto restart operation selection 0
H5-07 RTS control ON/OFF 1 L6-01 Torque detection selection 1 0
H6-01 Pulse train input function selection 0 L6-02 Torque detection level 1 150
H6-02 Pulse train input scaling 1440 L6-03 Torque detection time 1 0.1
Table 10.7 User Constants (Continued)
No. Name
Fac-
tory
Setting
Set-
ting
No. Name
Fac-
tory
Setting
Set-
ting

Table of Contents

Other manuals for YASKAWA Varispeed f7

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA Varispeed f7 and is the answer not in the manual?

YASKAWA Varispeed f7 Specifications

General IconGeneral
BrandYASKAWA
ModelVarispeed f7
CategoryInverter
LanguageEnglish

Related product manuals