6. Programming Features
65
The factory setting depends on the Inverter capacity (kVA).
1. Reduce the continuous output current when changing the
carrier frequency to 4 (10 kHz) for 200 V Class (1.5 kW
or more) and 400 V Class Inverters. Refer to the table
above for the reduced current.
Operation Condition
• Input power supply voltage:
3-phase 200 to 230 V (200 V Class)
Single-phase 200 to 240 V (200 V Class)
3-phase 380 to 460 V (400 V Class)
• Ambient temperature:
10 to 50°C
(Protection structure: open chassis type IP20)
Voltage
Class (V)
Capacity
(kW)
Initial Setting Maximum
Continuous
Output Cur-
rent (A)
Reduced
Current
(A)
Setting Carrier Fre-
quency (kHz)
200 V
Single-
phase or
3-phase
0.1 4 10 0.8 -
0.2 4 10 1.6
0.4 4 10 3.0
0.75 4 10 5.0
1.5 3 7.5 8.0 7.0
2.2 3 7.5 11.0 10.0
3.7 3 7.5 17.5 16.5
400 V
3-phase
0.2 3 7.5 1.2 1.0
0.4 3 7.5 1.8 1.6
0.75 3 7.5 3.4 3.0
1.5 3 7.5 4.8 4.0
2.2 3 7.5 5.5 4.8
3.0 3 7.5 7.2 6.3
3.7 3 7.5 8.6 7.6
NOTE