6. Programming Features
71
To select the 3-wire sequence, set terminal S3 (n37) to
0.
Failure to observe this warning may result in injury.
LOCAL/REMOTE Selection (Setting: 17)
Select the operation reference from either the Digital Operator or from
the settings of the RUN Command Selection (n02) and Frequency Ref-
erence Selection (n03). The LOCAL/REMOTE Selection can be used
only when stopped.
Open: Run according to the setting of RUN Command Selection
(n02) or Frequency Reference Selection (n03).
Closed: Run according to the frequency reference and RUN command
from the Digital Operator.
Example: Set n02=1, n03=2, n07=0.
Open: Run according to the frequency reference from multi-function
input terminal FR and RUN command from multi-function
input terminals S1 to S5.
Closed: Run according to the potentiometer frequency reference and
RUN command from the Digital Operator.
UP/DOWN Commands (Setting: n39 = 034)
When the FWD (REV) RUN command is ON, acceleration/deceleration
is enabled by inputting the UP or DOWN signal from multi-function
input terminals S4 and S5 without changing the frequency reference.
Operation can thus be performed at the desired speed. When UP/
DOWN commands are specified in n39, any function set in n38 is dis-
abled, terminal S4 is the input terminal for the UP command, and termi-
nal S5 is the input terminal for the DOWN command.
Multi-function Input Termi-
nal S4 (UP command)
Closed Open Open Closed
Multi-function Input Termi-
nal S5 (DOWN command)
Open Closed Open Closed
Operation Status Accel-
eration
Decel-
eration
Hold Hold
WARNING