IM 1C22H1-01E
7-4
7. BRAIN TERMINAL BT200 OPERATION
7.3 Setting Parameters Using the BT200
7.3.1 Parameter Summary
Instruments to which applicable:
F: Differential pressure transmitters EJA110, EJA120, EJA118W, EJA118N, EJA118Y, and EJA115
P: Pressure transmitters EJA310, EJA430, EJA438W, and EJA438N
L: Liquid level transmitters EJA210 and EJA220
No. Description
Model+capsule type
Tag number
Applica-
bility
PLF
01
02
T0705.EPS
Rewrita-
bility
16 alphanumerics
GOOD/ERROR
Remarks
Item
MODEL
TAG NO.
Self-diagnostic result
—
—
—
03 SELF CHECK
Measured data displayA
–5 to 110%
Menu nameDISPLAY
Output (in %)A10 OUTPUT (%)
–19999 to 19999Output (in engineering
units)
A11 ENGR.
OUTPUT
Unit specified in D30Amplifier temperatureA20 AMP TEMP
Unit specified in D30Capsule temperatureA21 CAPSULE
TEMP
—
Sensor typeB
16 uppercase alphanumerics
Menu nameSENSOR
TYPE
Model+spanB10 MODEL
—
Style numberB11 STYLE NO.
–32000 to 32000Lower range-limitB20 LRL
–32000 to 32000
Upper range-limitB21 URL
–32000 to 32000Minimum spanB30 MIN SPAN
—
—
—
—
—
Unit specified in D31*Static pressureA30 STATIC
PRESS
–32000 to 32000Input (indicated in
engineering DP unit)
A40 INPUT
GOOD/ERROR, CAP MODULE
FAULT, AMP MODULE FAULT,
OUT OF RANGE, OUT OF SP
RANGE*, OVER TEMP (CAP),
OVER TEMP (AMP),
OVER OUTPUT, OVER DISPLAY,
ILLEGAL LRV, ILLEGAL HRV,
ILLEGAL SPAN, and
ZERO ADJ OVER
Self-diagnostic
messages
A60 SELF CHECK
—
—
—
—
—
—
—
* In case of Model EJA120, static pressure cannot be measured. The display is always 0 MPa, but
this is not a measured value.
Maximum atatic
pressure
B40
Same as A60
MAX STAT.P.
Self-diagnostic
messages
—
—
B60 SELF CHECK
Setting dataC
16 alphanumerics
Menu nameSETTING
Tag numberC10 TAG. NO.
Selected from mmH
2
O, mmAq,
mmWG, mmHg, Torr, Pa, hPa, kPa,
MPa, mbar, bar, gf/cm
2
, kgf/cm
2
,
inH
2
O, inHg, ftH
2
O, psi, or atm
Measurement range
units
C20 PRESS UNIT
–32000 to 32000(but within
measurement range)
Measurement range,
lower range value
C21 LOW RANGE
—
Self-diagnostic
messages
C60 Same as A60SELF CHECK
—
—
—
—
–32000 to 32000(but within
measurement range)
Measurement range,
higher range value
C22 HIGH
RANGE
Selected from 0.2, 0.5, 1.0, 2.0,
4.0, 8.0, 16.0, 32.0, or 64.0 sec.
Damping time constantC30 AMP
DAMPING
Selected from OUT:LIN; DSP:LIN,
OUT:LIN; DSP:SQR,
OUT:SQR; DSP:SQR
Output mode and
integral indicator mode
C40 OUTPUT
MODE
0.0 to 20.0%
LINEAR/ZERO
Low cutD10 LOW CUT
Low cut modeD11 LOW CUT
MODE
NORMAL %/USER SET,
USER & %/INP PRES, PRES & %
Display selectionD20 DISP SELECT
—
Auxiliary setting data 1D Menu nameAUX SET 1
—
Default Value
As specified when ordered.
As specified when ordered.
As specified when ordered.
As specified when ordered.
2 s
As specified when ordered.
If not specified,
OUT: LIN; DSP: LIN.