IM 01C25T01-01E
3-9
3. OPERATION
3.4.4 Output Mode
The mode setting for the output signal and the integral
indicator can be performed independently.
The output mode for the output signal is set as speci-
fied in the order when the instrument is shipped.
Follow the procedure below to change the mode.
1
F0312.EPS
Call up the Xfer fnctn display.
EJX:YOKOGAWA
Xfer function
Linear
Linear
Sq root
DEL SET ESC ENTER
[1] Select Sq root, and press
ENTER (F4).
[2] Press SEND (F2) to send the
data to the transmitter, then
check to confirm that
disappears.
(ENTER)
1. Device setup
3. Basic setup
5. Xfer fnctn
(SEND)
SEND
Example: To change the mode from Linear to Sq root.
3.4.5 Damping Time Constant Setup
The damping time constant is set as specified in the
order when the instrument is shipped. Follow the
procedure below to change the damping time constant.
The damping time constant for the amplifier assembly
can be set here. The damping time constant for the
entire transmitter is the sum of the values for the
amplifier assembly and the capsule assembly.
Any number from 0.00 to 100.00 can be set for the
damping time constant. Note that setting the quick
response parameter ON enables you to set the time
constant between 0.00 and 0.49 seconds.
1
Call up the Quick resp display to set the value to less
than 0.5 seconds.
EJX:YOKOGAWA
Quick resp
Off
Off
On
HELP DEL ESC ENTER
Select On and press ENTER (F4).
(ENTER)
2
EJX:YOKOGAWA
Signal condition
7 Low cut mode
8 H/L Swap Normal
9 Bi-dir mode Off
Quick resp On
T.Z. Cmp menu
HELP SEND HOME ENTER
Press SEND (F2) to send the data
to the transmitter.
1. Device setup
4. Detailed setup
2. Signal condition
Quick resp
Example: To change from 2.0 seconds to 0.5 seconds
1
F0313.EPS
Call up the Pres Damp display.
EJX:YOKOGAWA
Pres Damp
2.00 sec
0.5
HELP DEL ESC ENTER
Enter 0.5 and press ENTER (F4).
(ENTER)
‘0 . 5’
2
EJX:YOKOGAWA
Basic Setup
3 Re-range
4 Device information
5 Xfer fncfn
6 Pres Damp 0.50 sec
7 Low cut 10.00 %
HELP SEND HOME ENTER
Press SEND (F2) to send the data
to the transmitter.
1. Device setup
3. Basic setup