IM 01C25T01-01E
5-1
5. PARAMETER SUMMARY
5. PARAMETER SUMMARY
Analog output AO alm typ Analog output alarm type High or Low R 1, 4, 3, 2, 5
AO lower limit Lower limit of analog output 3.6000 to 21.6000 mA 3.6000 mA W 1, 4, 3, 2, 7
AO upper limit Upper limit of analog output 3.6000 to 21.6000 mA 21.6000 mA W 1, 4, 3, 2, 8
Auto recover Auto-recover from hardware error Off or On On W 1, 4, 3, 2, 6
Analog output trim Clear D/A trim Reset analog output trim M 1, 2, 3, 2, 3
D/A trim Analog output trim with ammeter M 1, 2, 3, 2, 1
Scaled D/A trim Analog output trim with voltmeter M 1, 2, 3, 2, 2
Bi-directional mode Bi-dir mode Bi-directional mode Off or On Off W 1, 4, 2, 9
Burst mode Burst mode Burst mode Off or On Off W 1, 4, 3, 3, 3
Burst operation option Burst option Burst option PV, % range/current, or Process vars/cmt W 1, 4, 3, 3, 4
Damping Pres Damp Damping time constant at amplifier 0.00 to 100.00 sec As specified or W 1, 3, 6
2.00 sec
Quick resp Quick response On or Off Off W 1, 4, 2, ↓
Date Date Date **/**/** W 1, 3, 4, 1
Descriptor Descriptor Descriptor 16 alphanumerics As specified W 1, 3, 4, 2
Device information Dev id Device ID R 1, 4, 5, 1, ↓, 6
Distributor Yokogawa R 1, 4, 5, 1, ↓, 7
Drain vent matl Drain and vent plug material W 1, 4, 5, 2, 5
Extra No. Customization number R 1, 4, 5, 1, ↓, 4
Ext SW External zeroing permission Disabled or Enabled Enabled W 1, 4, 5, 1, 9
Fill fluid Fill fluid W 1, 4, 5, 2, 2
Final asmbly num Final assembly number W 1, 4, 5, 1, ↓, 5
Fld dev rev Field device revision R 1, 4, 5, 1, ↓, 2
Gasket matl Gasket material W 1, 4, 5, 2, 3
Isoltr matl Capsule material W 1, 4, 5, 2, 1
LSL Lower sensor limit R 1, 3, 3, 1, 4
Mftr Date Manufactured date R 1, 4, 5, 1, ↓, 3
Min Span Minimum span R 1, 3, 3, 1, 6
Model 1 Memo field for MS code 1 16 alphanumerics W 1, 4, 5, 1, 5
Model 2 Memo field for MS code 2 16 alphanumerics W 1, 4, 5, 1, 6
Model 3 Memo field for MS code 3 16 alphanumerics W 1, 4, 5, 1, 7
Num of RS Number of remote seal W 1, 4, 5, 2, 9
Process Conn matl Process connection material W 1, 4, 5, 2, 4
Process Conn size Process connection size W 1, 4, 5, 2, 8
Process Conn type Process connection type W 1, 4, 5, 2, 6
RS fill fluid Fill fluid of remote seal W 1, 4, 5, 2, ↓
RS Isoltr matl Remote seal material W 1, 4, 5, 2, 7
RS type Remote seal type W 1, 4, 5, 2, ↓
Serial No. Serial number R 1, 4, 5, 1, ↓, 2
Software rev Software revision R 1, 4, 5, 1, ↓, 3
Style No. Style number Style number of product R 1, 4, 5, 1, ↓, 1
Universal rev Universal revision R 1, 4, 5, 1, ↓, 1
USL Upper sensor limit R 1, 3, 3, 1, 5
Display setup Bar indicator Bar indicator Off or On On W 1, 4, 4, 5
Disp Out 1 LCD output 1 Pres, Pres %, Engr Pres, SP, or SP % Pres % W 1, 4, 4, 1, 1
Disp Out 2 LCD output 2 Pres, Pres %, Engr Pres, SP, SP %, or Not used Not used W 1, 4, 4, 1, 2
Disp Out 3 LCD output 3 Pres, Pres %, Engr Pres, SP, SP %, or Not used Not used W 1, 4, 4, 1, 3
Disp Out 4 LCD output 4 Pres, Pres %, Engr Pres, SP, SP %, or Not used Not used W 1, 4, 4, 1, 4
Disp Pres % fnctn % display mode Linear or Sq root As specified or W 1, 4, 4, 2, 1
Linear
Disp Pres % Reso % display resolution Normal or High resolution Normal W 1, 4, 4, 2, 2
Engr exp Exponents ---, !10, !100, or !1000 As specified or W 1, 4, 4, 4, 3
---
Engr LRV User set lower range value 32000 to 32000, unit specified in Set Engr Unit As specified W 1, 4, 4, 4, 1
Engr point Decimal place for user set 0 to 4 2 W 1, 4, 4, 4, 5
Engr URV User set upper range value 32000 to 32000, unit specified in Set Engr Unit As specified W 1, 4, 4, 4, 2
Modify Engr Unit User set engineering unit As specified M 1, 4, 4, 4, 7
Pres disp point Decimal place for pressure 0 to 4 2 W 1, 4, 4, 2, 3
Set Engr Unit Engineering unit select See section 3.5.3d M 1, 4, 4, 4, 6
SP disp point Decimal place for static pressure 0 to 4 2 WD 1, 4, 4, 3, 1
Error log Error log Clear Clear error records M 1, 2, 4, 2
Error log view Error records Log1 (latest) to log4 M 1, 2, 4, 1
Loop test Loop test Test output setting Within AO lower and upper limits M 1, 2, 2
Low cut Low cut Low cut 0.00 to 20.00% 10.00% W 1, 3, 7
Low cut mode Low cut mode Linear or Zero Linear W 1, 3, 8
Message Message Message 32 alphanumerics As specified W 1, 3, 4, 3
Number of requested Num req preams Number of requested preambles R 1, 4, 3, 3, 2
preambles
Piping orientation H/L Swap Impulse piping accessing direction Normal or Reverse Normal WD 1, 3, 9
Poll address Poll addr Poll address for multidrop use 0 to 15 0 W 1, 4, 3, 3, 1
Process Alert Digital Output Display of contact output Off or On Off RA 1, 4, 3, 4, 7, 1
DO Select Contact output select Off, P Alarm, SP Alarm, P or SP Alarm Off WA 1, 4, 3, 4, 7, 2
DO Signal type Signal type select On When Al Detect or Off When Al Detect
On When Al Detect
WA 1, 4, 3, 4, 7, 3
DO Test Test output contact Off, On, or Exit MA 1, 4, 3, 4, 7, 4
Hi Alert Val High side alert value of pressure LSL10% to USL"10% minus 5% hysteresis W 1, 4, 3, 4, 2, 1
Lo Alert Val Low side alert value of pressure LSL10% to USL"10% plus 5% hystereis W 1, 4, 3, 4, 2, 2
Pres Alert mode Alert mode for pressure Off, Hi Al Detect, Lo Al Detect, or Hi/Lo Al Detect Off W 1, 4, 3, 4, 1
SP Alert mode Alert mode for static pressure Off, Hi Al Detect, Lo Al Detect, or Hi/Lo Al Detect Off WD 1, 4, 3, 4, 3
SP Hi Alert Val High side alert value of static pressure SP LSL10% to SP USL"10% minus 5% WD 1, 4, 3, 4, 4, 1
hysteresis
SP Lo Alert Val Low side alert value of static pressure SP LSL10% to SP USL"10% plus 5% hystereis WD 1, 4, 3, 4, 4, 2
Te mp Alert mode Alert mode for temperature Off, Hi Al Detect, Lo Al Detect, or Hi/Lo Al Detect Off W 1, 4, 3, 4, 5
Te mp Hi Alert Val High side alert value of temperature 50 to 130 120 degC W 1, 4, 3, 4, 6, 1
Te mp Lo Alert Val Low side alert value of temperature 50 to 130 40 degC W 1, 4, 3, 4, 6, 2
Function Label Item Contents Default value Handling
*1: Handling: R#Read only, W#Read & Write, M#Method, A#Applicable for option code AL, D#Applicable for differential pressure transmitters. Do not change these parameters
for pressure transmitters.
Fast key
sequences
T0501.EPS