ecifications section in each user’s manual.
Fast key
sequences
T0502.EPS
Process variables AO Analog output current 3.6000 to 21.6000 mA R 1, 1, 3
Engr Disp User scaled value 32000 to 32000, unit specified in Set Engr Unit R 1, 1, 7
Engr Unit User set engineering unit Unit specified in Set Engr Unit R 1, 1, 9
Pres Measured pressure 32000 to 32000, unit specified in Unit R 1, 1, 1
Pres % Measured pressure in % 2.50 to 110.00% R 1, 1, 2
Snsr temp Capsule temperature Unit specified in Temp Unit R 1, 1, 6
SP Measured static pressure 32000 to 32000, unit specified in SP Unit RD 1, 1, 4
SP % Measured static pressure in % 10.0 to 110.00% RD 1, 1, 5
Rerange Apply values Rerange for measured pressure 4 mA, 20 mA, or Exit M 1, 3, 3, 2
LRV Lower range value 32000 to 32000 within measurement range As specified W 1, 3, 3, 1, 1
URV Upper range value 32000 to 32000 within measurement range As specified W 1, 3, 3, 1, 2
Self test Self test Self-diagnostics See Chapter 4 M 1, 2, 1, 2
Sensor trim Clear P snsr trim Reset pressure trim to factory setting M 1, 2, 3, 3, 5, 3
Clear SP snsr trim Reset SP trim to factory setting MD 1, 2, 3, 4, 4, 3
P LTD Lower pressure trim deviation R 1, 2, 3, 3, 5, 1
P LTP Lower temperature trim point R 1, 2, 3, 3, 3
P UTD Upper pressure trim deviation R 1, 2, 3, 3, 5, 2
P UTP Upper temperature trim point R 1, 2, 3, 3, 4
Pres trim Pressure trim M 1, 2, 3, 3, 2
Pres Zero trim Zeroing M 1, 2, 3, 3, 1
SP LTD Lower SP trim deviation RD 1, 2, 3, 4, 4, 1
SP LTP Lower SP trim point RD 1, 2, 3, 4, 2
SP UTD Upper SP trim deviation RD 1, 2, 3, 4, 4, 2
SP UTP Upper SP trim point RD 1, 2, 3, 4, 3
Static Pres trim Static pressure trim MD 1, 2, 3, 4, 1
Tr im Date Trim information **/**/** W 1, 2, 3, 5, 2
Tr im Desc Trim information 16 alphanumerics W 1, 2, 3, 5, 4
Tr im Loc Trim information 8 alphanumerics W 1, 2, 3, 5, 3
Tr im Who Trim information 8 alphanumerics W 1, 2, 3, 5, 1
Signal characterizer Num of points Number of coordinates 0 to 9 9 W 1, 4, 2, ↓, 2
Point setting Coordinates editor M 1, 4, 2, ↓, 3
S.C. Signal characterizer permission Disabled or Enabled Disabled W 1, 4, 2, ↓, 1
X End End point of X 100.00% R 1, 4, 2, ↓, 6
X Start Start point of X 0.00% R 1, 4, 2, ↓, 4
Y End End point of Y 100.00% R 1, 4, 2, ↓, 7
Y Start Start point of Y 0.00% R 1, 4, 2, ↓, 5
Static pressure A/G Select Gauge/abs select for static pressure Gauge or Absolute Absolute WD 1, 4, 1, 2, 7, 4, 1
setup Atm. Pres value Conversion coefficient 101.3 kPa WD 1, 4, 1, 2, 7, 4, 2
SP H/L Select H/L select for static pressure High or Low High WD 1, 4, 1, 2, 7, 5
SP Apply values Rerange for static pressure "0%, 100%, or Exit" MD 1, 4, 1, 2, 7, 1, 2
SP Damp Damping time constant for SP 0.00 to 100.00 sec 2.00 sec WD 1, 4, 1, 2, 7, 3
SP LRV Lower range value for static pressure 32000 to 32000 within measurement range 0.0 MPa WD 1, 4, 1, 2, 7, 1, 1, 1
SP LSL Lower sensor limit for static pressure RD 1, 4, 1, 2, 7, 1, 1, 4
SP Min Span Minimum span for static pressure RD 1, 4, 1, 2, 7, 1, 1, 6
SP URV Upper range value for static pressure*
2
32000 to 32000 within measurement range WD 1, 4, 1, 2, 7, 1, 1, 2
SP USL Upper sensor limit for static pressure RD 1, 4, 1, 2, 7, 1, 1, 5
Status Status group 1 Device status information for hardware R 1, 2, 1, 1, 1
Status group 2 Device status information for hardware R 1, 2, 1, 1, 2
Status group 3 Device status information for process R 1, 2, 1, 1, 3
Status group 4 Device status information for process R 1, 2, 1, 1, 4
Status group 5 Device status information for process R 1, 2, 1, 1, 5
Status group 6 Device status information for settings R 1, 2, 1, 1, 6
Status group 7 Device status information for settings R 1, 2, 1, 1, 7
Tag Tag Tag number 8 alphanumerics As specified W 1, 3, 1
Temperature T.Z. Cmp mode Temperature compensation mode Off or On Off W 1, 4, 2, ↓, 1
compensation Temp Zero Zero shift compensation 99.999 to 99.999%/degC 0.000%/degC W 1, 4, 2, ↓, 2
Temperature sensor Amp temp Amplifier temperature R 1, 4, 1, 3, 2
Snsr temp Capsule temperature R 1, 4, 1, 3, 1
Temp Unit Temperature setting unit degC, degF, or Kelvin degC W 1, 4, 1, 3, 3
Test key Test Key Special maintenance parameter M 1, 4, 6
Transfer function Xfer fnctn Output mode Linear or Sq root As specified or W 1, 3, 5
Linear
Unit Unit Measurement range unit See section 3.4.2 As specified or W 1, 3, 2
kPa
SP Unit Static pressure unit See section 3.5.5 MPa WD 1, 4, 1, 2, 3
Write protect menu Enable wrt 10min Write protect release 8 alphanumerics M Hot key, 2, 2
New password User set password for write protect 8 alphanumerics M Hot key, 2, 3
Software seal Software seal Keep or Break Keep R Hot key, 2, 4
Write protect Write protect indicator Yes or No No R Hot key, 2, 1