Loading...
IM 01C25T01-01E
3-25
3. OPERATION
F0345.EPS
(ENTER)
EJX:
S.C
Disabled
Disabled
Enabled
HELP DEL ESC ENTER
Select Enabled, and press ENTER
(F4).
1. Device setup
4. Detailed setup
2. Signal condition
S.C. menu
1. S.C.
Example: Set the signal characterizer to Enabled.
EJX:
S.C. menu
1 S.C. Enabled
2 Num of points 5
3 Point setting
4 X Start 0.00 %
5 Y Start 0.00 %
HELP SEND HOME ENTER
Press SEND (F2) to send the data
to the transmitter, then check to
confirm that disappears.
(SEND)
SEND
1
2
3.5.15 Process Alarm
The function is used to display the alarm codes when
the input pressure exceeds the specified value within
the calibration range. The same is available for the
input static pressure and the capsule temperature on the
pressure sensor. Refer to table 4.2.1 Alarm Message
Summary for the specific alarm code to be generated.
F0346.EPS
(ENTER)
EJX:
Pres Alert mode
Off
Off
Hi. Al Detect
Lo. Al Detect
Hi/Lo. Al Detect
HELP DEL ESC ENTER
Select Hi. Al Detect, and press
ENTER (F4).
1. Device setup
4. Detailed setup
3. Output condition
4. Process Alerts
1. Pres Alert mode
Example: Set the alert mode from OFF to Hi. Al Detect for
the input pressure.
EJX:
Process Alerts
1 Pres Alert mode
2 Config Pres Alerts
3 SP Alert Mode Off
4 Config SP Alerts
5 Temp Alert Mode
HELP SEND HOME ENTER
Press SEND (F2) to send the data
to the transmitter, then check to
confirm that disappears.
(SEND)
SEND
1
2
F0347.EPS
(ENTER)
EJX:
Hi Alert Val
100.000 kPa
75
HELP DEL ESC ENTER
Enter 75, and press ENTER (F4).
1. Device setup
4. Detailed setup
3. Output condition
4. Process Alerts
2. Config Pres Alerts
1. Hi Alert Val
Example: Set the higher alert value of 75 for alarm
generation.
EJX:
Config Pres Alerts
1 Hi Alert Val
2 Lo Alert Val
3 LSL -100.000 kPa
4 USL 100.000 kPa
HELP SEND HOME ENTER
Press SEND (F2) to send the data
to the transmitter, then check to
confirm that disappears.
(SEND)
SEND
1
2
‘ 75 ’