IM 01C25T02-01E
9-4
9. PARAMETER LISTS
T0902-2.EPS
Write
Mode
Explanation
Factory
Default
Relative
Index
Parameter NameIndex
2018
CAL_MIN_SPAN Minimum span of
capsule
18
The minimum calibration span value allowed.
2019 CAL_UNIT kPa19
The engineering unit for the calibrated values.
2020
SENSOR_TYPE Silicon resonant
20
The type of sensor.
2021
SENSOR_
RANGE
Range of
capsule
21
The High and Low range limit values, engineering units code
and the number of digits to the right of the decimal point for
the sensor.
2022
SENSOR_SN Serial No.
22
Serial number.
2023
SENSOR_CAL_
METHOD
O/S103: factory trim
standard
calibration
23
The method of the last sensor calibration.
100=volumetric
101=static weight
102=dynamic weight
103=factory trim standard calibration
104=user trim standard calibration
105=factory trim special calibration
106=user trim special calibration
255=others
2024 SENSOR_CAL_
LOC
O/S24
Set/indicate the location of the last sensor calibration.
2025
SENSOR_CAL_
DATE
O/S
25
Set/indicate the date of the last sensor calibration.
2026 SENSOR_CAL_
WHO
O/S26
Set/indicate the name of the person responsible for the last
sensor calibration.
2027
SENSOR_
ISOLATOR_MTL
Unkown
27
Defines the construction material of the isolating diaphragms.
2028
SENSOR_FILL_
FLUID
Unkown
28
Defines the type of fluid used in the sensor.
2029
SECONDARY_
VALUE
29
Static pressure (high pressure side) value and status
2030
SECONDARY_
VALUE_UNIT
1133 (KPa)
30
The engineering unit of static pressure (high pressure side).
This unit is linked to XD_SCALE.unit of AI blocks
2031
CAL_
DEVIATION_HI
O/S0
31
Deviation value for span adjustment.
2032
CAL_
DEVIATION_LO
O/S0
32
Deviation value for zero adjustment.
2033
EXTERNAL_
ZERO_TRIM
O/S0
33
Permission of external zero-adjustment
2034
PRIMARY_
VALUE_FTIME
O/S2
34
Damping time constant for primary value
2035
TERTIARY_
VALUE
35
Value and status of static pressure at low side
2036
SP_VALUE_
TYPE
O/S109
(absolute
pressure)
36
Select the type of measurement for static pressure, absolute
or gauge
2013
PRIMARY_
VALUE_TYPE
O/S
107: differential
pressure
108: gauge pressure
109: absolute
pressure
13
The type of measurement represented by primary value.
Followings are available for EJX:
107=differential pressure
108=gauge pressure
109=absolute pressure
2014 PRIMARY_
VALUE
14
The measured value and status available to the function
block.
2015
PRIMARY_
VALUE_RANGE
Range of
capsule
15
The High and Low range limit values, engineering units code
and the number of digits to the right of the decimal point to be
used to display the primary value.
2016 CAL_POINT_HI O/SMax range16
The highest calibrated value.
2017
CAL_POINT_LO O/S0
17
The lowest calibrated value.