IM 01C25T02-01E
9-5
9. PARAMETER LISTS
T0902-3.EPS
Write
Mode
Explanation
Factory
Default
Relative
Index
Parameter NameIndex
2043
CAL_SP_
DEVIATION_LO
O/S0
43
Deviation value for zero adjustment of static pressure
2044
SP_VALUE_FTIME
O/S2
44
Damping time constant for static pressure
2045
ATM_PRESS O/S101.325
45
Atmosphere pressure value used to obtain gauge pressure
value from absolute pressure.
2046
CLEAR_CAL O/S0
46
Reset zero and span adjustment to factory calibrated values
for pressure, static pressure, and or all.
2047
CAP_TEMP_VAL
–
47
Measured capsule temperature value and status.
2048
CAP_TEMP_
RANGE
–50.0 to 130.0°C
48
High and low range limit values, engineering units, decimal
point place for capsule temperature.
2051
MODEL –Model code
51
The model code.
2052
SPECIAL_
ORDER_ID
–Special order
number
52
Identification number of special order.
2049
AMP_TEMP_VAL
–
49
Measured Amplifier temperature value and status.
2050
AMP_TEMP_
RANGE
–50.0 to 95.0°C
50
High and low range limit values, engineering units, decimal
point place for Amplifier temperature.
2053
MANUFAC_DATE
O/S053
Date of production
2054
CAP_GASKET_MTL
O/S
Depend on Specify
54
Material of capsule gasket
2055
FLANGE_MTL O/S
Depend on Specify
55
Material of flange
2056
D_VENT_PLUG O/S
Depend on Specify
56
Material of drain or vent plug
2057
FLANGE_TYPE O/S
Depend on Specify
57
Flange type
2058
REM_SEAL_
ISOL_MTL
O/SDepend on
Specify
58
Material of isolating diaphragms for remote seal
2059
FLANGE_SIZE O/S
Depend on Specify
59
Flange size
2060
REM_SEAL_
NUM
O/SDepend on
Specify
60
Number of remote seal
2061
REM_SEAL_
FILL_FLUID
O/SDepend on
Specify
61
Types of fill fluid in remote seals.
2062
REM_SEAL_
TYPE
O/SDepend on
Specify
62
Types of remote seals
2063
ALARM_SUM –Alarm Disable
63
The current alert status, unacknowledged states, unreported
states, and disabled states of the alarms associated with the
function block.
65 2065 MS_CODE Null – Model suffix and codes
66 2066 DIAG_MODE – Not used for EJX
67 2067 DIAG_PERIOD – Not used for EJX
68 2068 DIAG_PRI – Not used for EJX
69 2069 DIAG_ERR – Not used for EJX
64 2064
AUTO_RECOVERY
1 (ON) O/S Permission of auto recovery from sensor errors
2037
SP_VALUE_
RANGE
–Range of
capsule
37
High and low range limit values, engineering units, and
decimal point place for static pressure.
2038
CAL_SP_
POINT_HI
O/S16
38
The highest calibrated value for static pressure
2039
CAL_SP_
POINT_LO
O/S0
39
The Lowest calibrated value for static pressure
2040
CAL_SP_MIN_
SPAN
–1.0
40
The minimum calibration span allowed for static pressure
2041
CAL_SP_UNIT –1133 (KPa)
41
The calibrated engineering unit for static pressure. This unit is
linked to XD_SCALE.unit of AI blocks
2042 CAL_SP_
DEVIATION_HI
O/S042
Deviation value for span adjustment of static pressure