<7.ErrorsandCountermeasures>
38
IM01C25A01-01E
Table7.2 AlarmMessageSummary(ForEJX910AandEJX930A,HARTprotocoltype)
Integral
indicator
Cause
4-20mAOutput
operationduringerror
Countermeasure
AL.01
CAP.ERR
Sensorproblem. Outputsthesignal(HighorLow)set
withburnoutdirectionswitch.
[statusoutput:undened]
Replacecapsuleiftheerrorrecurs
afterthetransmitterisrestarted.
Capsuletemperaturesensorproblem. Replacecapsule.
CapsuleEEPROMproblem.
AL.02
AMP.ERR
Ampliertemperaturesensorproblem. Replaceamplier.
AmplierEEPROMproblem.
Amplierproblem.
A/DConverterproblem.
AL.03
ET.ERR
Externaltemperaturesensor
disconnection.
Checkexternaltemperaturesensor.
— NodeviceIDisfound. Continuestooperateandoutput. Replaceamplier.
AL.10
PRESS
Differentialpressureisoutside
measurementrangelimitofcapsule.
WhenPVisPres
OutputAOupperlimitorAOLower
limit.
Checkinputorreplacecapsulewhen
necessary.
AL.11
ST.PRSS
Staticpressureexceedslimit. WhenPVisSP
OutputAOupperlimitorAOLower
limit.
AL.12
CAP.TMP
Capsuletemperatureisoutsiderange
(–50to130°C).
Continuestooperateandoutput. Useheatinsulationormakelagging
tokeeptemperaturewithinrange.
AL.13
AMP.TMP
Ampliertemperatureisoutsiderange
(–50to95°C).
AL.14
EXT.TMP
Externaltemperatureisoutsiderange. WhenPVisET
OutputAOupperlimitorAOLower
limit.
AL.15
EXT.TMP
Externaltemperaturesensorresistance
isoutspecication.
AL.16PLS Pulseoutputisoutspecication. Continuestooperateandoutput. Checksettingsandchangethem.
AL.30
PRS.RNG
Differentialpressureexceedsspecied
range.
WhenPVisPres.
OutputAOupperlimitorlowerlimit.
Checkinputandrangesetting,and
changethemasneeded.
AL.31
SP.RNG
Staticpressureexceedsspecied
range.
WhenPVisSP
OutputAOupperlimitorlowerlimit.
AL.32
F.RNG
Flowexceedsspeciedrange. WhenPVisFlow
OutputAOupperlimitorlowerlimit.
AL.33
ET.RNG
Externaltemperatureexceedsspecied
range.
WhenPVisET
OutputAOupperlimitorlowerlimit.
AL.35P.HI Inputpressureexceedsspecied
threshold.
Continuestooperateandoutput. Checkinput.
AL.36P.LO
AL.37SP.HI Inputstaticpressureexceedsspecied
threshold.
AL.38SP.LO
AL.41F.HI Inputowexceedsspeciedthreshold.
AL.42F.LO
AL.43ET.HI Inputexternaltemperatureexceeds
speciedthreshold.
AL.44ET.LO
AL.50P.LRV Speciedvalueisoutsideofsetting
range.
Holdsattheoutputvaluethatexisted
immediatelybeforetheerroroccurred.
Checksettingsandchangethemas
needed.
AL.51P.URV
AL.52P.SPN
AL.53P.ADJ Continuestooperateandoutput. Adjustsettingsandchangethemas
needed.
AL.54
SP.RNG
Holdsattheoutputvaluethatexisted
immediatelybeforetheerroroccurred.
Checksettingsandchangethemas
needed.
AL.55
SP.ADJ
Continuestooperateandoutput. Adjustsettingsandchangethemas
needed.
AL.56
ET.RNG
Holdsattheoutputvaluethatexisted
immediatelybeforetheerroroccurred.
Checksettingsandchangethemas
needed.
AL.57
ET.ADJ
Continuestooperateandoutput. Adjustsettingsandchangethemas
needed.
AL.58
FL.ADJ
Holdsattheoutputvaluethatexisted
immediatelybeforetheerroroccurred.
Checksettingsandchangethemas
needed.
AL.59
PLS.ADJ
Speciedvalueisoutsideofsetting
pulseoutput.
Normalcalculation.
— UnderTemperatureFixMode.PVisET Temp.OutputFixat4mA.
LeavefromTemperatureFixMode.