EasyManua.ls Logo

YOKOGAWA ProSafe-RS

YOKOGAWA ProSafe-RS
207 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2. Transportation, Storage and Installation
2-47
TI 32P01J10-01EN
Mar. 29, 2019-00
Example of Mounting N-IO Nodes (Mixture of Intrinsic Safety Barrier and Non-
Intrinsic Safety Barrier) in a Junction Box
Temperature conditions
In this example, the ambient temperature is assumed to be the following.
Junction Box ambient temperature 50 °C or less
Maximum numbers of units that can be mounted
Type Model Number of units that can be mounted per side
Per junction box
NIU S2NN30D Up to 1
IOBP S2BN1D Up to 2 (1 row × 2 shelves)
IOBP_IS S2BN4D or S2BN5D Up to 1 (1 row × 1 shelf)
Other
Heat-generating device
(*1)
heat generation: 20 W or less
*1: The device to be mounted shall be selected from those that have the ambient temperature range of +15 °C or more.
Heat-generating devices other than the above shall not be mounted in the junction box.