4.InstallationSpecications
4-4
TI 32P01J10-01EN
Measurement Conditions
Input voltage: 132/264 V AC, 50 Hz, and 24 V DC
Line impedance: Approx. 0.4 ohms (external line impedance and internal impedance)
Turn-on timing: At 50 Hz, 90º or 5 ms after the AC zero-crossing point (60 Hz data are almost the
same as the 50 Hz data shown above.)
Note
The timing of the maximum primary/secondary in-rush current varies with devices.
The restart in-rush current after a momentary power failure exceeds the above data and its
timing is also di󰀨erent.
For a system composed of multiple pieces of equipment, the in-rush current is normally
smaller than the total of the in-rush currents by individual pieces of equipment.