IM 05P02D41-11EN page 4/14
E1-Terminal Area
301-306
E4-Terminal Area
501-506
Program patterns can be selected according to
the combination of ON and OFF contact inputs.
Program pattern no.
1 2 3 4
DI41 ON OFF ON OFF
DI42 OFF ON ON OFF
DI43 OFF OFF OFF ON
(Suffix code: Type 2=1)
Contact input
External contact input
DI41
DI42
DI43
DI44
DI45
COM
Common
DI41
DI42
COM
+5V
+5V
No-voltage
contact
Transistor contact
Contact rating: 12 V DC, 10 mA or more
DI43
+5V
DI44
+5V
DI45
+5V
Factory default: No function
Factory default: No function
UP UP
501
502
503
504
505
506
501
502
503
504
505
506
Function can be assigned to the
terminals with no function.
DI
Bit-0 of
program pattern number
Bit-1 of
program pattern number
Bit-2 of
program pattern number
(Suffix code: Type 2=1)
Contact output
External contact output
DO12
DO11
DO13
DO14
DO15
COM
Common
UP
301
302
303
304
305
306
DO
Transistor contact rating: 24 V DC, 50 mA
Function can be changed.
Time event-3 output
Time event-4 output
Alarm-2
Alarm-1
Time event-2 output
(Suffix code: Type 3=2)
Ethernet communication (with gateway function)
10BASE-T/100BASE-TX
RJ45 connector
Color
Lit
Unlit
Amber
100M bps
10M bps
Green
Linked
Active
Link failure
Color
Lit
Blink
Unlit
Upper side LED (baud rate)
Lower side LED (link activity)
RS-485
RSB(+)
RSA(-)
SG
407
408
409
ETHR
RS-485
SDB(+)
SDA(-)
RDB(+)
RDA(-)
SG
RS
-
485 communication
(Suffix code:
Type 3=1)
407
408
409
410
411
RS485
(Suffix code: Type 3=4)
PROFIBUS-DP communication (with Modbus master)
Pin
1
2
Signal name Description
VP
RxD/TxD-P
3 RxD/TxD-N
4 DGND
5 SHIELD
+5V bus power
Data signal
(positive data receive/transmit)
Data signal
(negative data recive/transmit)
Signal ground
Shield ground
RS-485
RSB(+)
RSA(-)
SG
407
408
409
PROF
If the UT is located at the end
of a segment for the
PROFIBUS
communication wiring,
terminating resistors are
separately needed.
These are to be prepared by
users. (390 Ω: 2 pcs. 220 Ω:
1 pc., or an active
terminator.)
VP
RxD/TxD-P
Data
line
Data
line
390Ω
220Ω
390Ω
RxD/TxD-N
DGND
CHK
RDY
ERR
1
2
3
4
5
LED
CHK
(red)
RDY
(green)
Lit
Unlit
ERR
(red)
User profile error Normal
Normal
Not connected, or
communication
failure (flashing)
Normal
Communicating
successfully
No electricity, or
Communication
failure
E3-Terminal Area
401-412
(Suffix code: Type 3=5)
DeviceNet communication (with Modbus master)
RS-485
RSB(+)
RSA(-)
SG
407
408
409
DNET
If the UT is located at
the end of a segment
for the DeviceNet
communication wiring,
terminating resistors
are separately needed.
These are to be
prepared by users.
(121 Ω: 1 pc.)
CAN_H
CAN_L
121Ω
LED
CHK
(red)
MNS
(green
/red)
Lit/flashing
Unlit
User profile error
Normal
Pin
1
2
Signal name Description
CAN_H
CAN_L
3
V+
4
V-
5
DRAIN
RX/TX + signal
RX/TX - signal
Shield/Drain wire
DeviceNet power supply 24V
DeviceNet power supply common
Normal, communicating
successfully (green, lit).
Not connected (green, flashing).
Critical link failure (red, lit).
Connection timeout (red, flashing)
At power-on/Communication
faulted (green/red, flashing)
No electricity
CHK
MNS
1
2
3
4
5
(Suffix code: Type 3=3)
CC-Link communication (with Modbus master)
RS-485
RSB(+)
RSA(-)
SG
407
408
409
CC-L
If the UT is located at
the end of a segment
for the CC-Link
communication wiring,
terminating resistors
are separately needed.
These are to be
prepared by users.
(110 Ω: 1 pc.)
DA
DB
110Ω
LED
CHK
(red)
L ERR
(red)
L RUN
(green)
Lit
Unlit
User profile error/
Address error
Normal
Normal
Pin
1
2
Signal name Description
DA
DB
3 DG
4
SLD
5
FG
RX/TX + signal
RX/TX - signal
Flame ground
RX/TX signal ground
Shield
Normal
Communicating successfully
Communication failure
(CRC error)
No carrier
detected/
Communication
timeout
CHK
L RUN
L ERR
1
2
3
4
5
E4-terminal area
E3-terminal area
E1-terminal area
101
102
103
104
105
106
107
108
109
110
111
501
502
503
504
505
506
507
508
509
510
511
512
407
401
408
409
410
411
412
301
302
303
304
305
306
201
202
203
204
205
206
207
208
210
211
212
101
-112
501
-512
401
-412
301
-306
201
-212
112
■ UP35A(Continuedfrompage3) ■ UP32A
E1-terminal area
111
301
302
303
304
305
306
307
308
309
310
311
312
201
202
203
204
205
206
207
208
209
210
101
102
103
104
105
106
107
108
109
110
211
212
101
-112
301
-312
201
-212
112
(Suffix code: Type 1=-2)
ALM
(Equipped
as standard)
Contact output
External contact output (relay)
AL3
AL2
AL1
Relay contact rating: 240 V AC, 1 A
30 V DC, 1 A (resistance load)
PV event-2 output
Time event-1 output
PV event-1 output
Common
Common
Common
UP
104
105
106
107
108
109
PV
PV input
TC input RTD input
Voltage (mV, V) input
A
+
-
+
-
Current (mA) input
+
-
B
b
as standard)
202
203
201
202
203
202
203
203
204
Factory default: PV input
type is undefined.
OUT
(Suffix code: Type1=-0)
Control output
101
102
Relay contact output
103
NC
NO
COM
Contact rating: 250 V AC, 3 A
30 V DC, 3 A (resistance load)
Terminal wiring differs in Heating/cooling
control and Position proportional control.
Refer to the terminals of Position
proportional control output and
Heating/cooling control output below.
Factory default: Control output is relay.
OUT
Current/voltage pulse output
0-20 mA DC,
4-20 mA DC,
Voltage pulse (12 V)
+
Retransmission output
+
-
Default: 4-20 mA DC
Default: Undefined
0-20 mA DC,
4-20 mA DC
Control output
(Suffix code: Type1=-0, -1 or -2)
15 V DC loop power supply
14.5-18.0 V DC
(Max. 21 mA DC)
+
-
207
208
207
-
208
207
208
Can be used for retransmission output or 15 V DC loop power supply when
current/voltage pulse output is not used for control output.
Current output range can be changed.
In Position proportional type, can be used for retransmission output or 15 V
DC loop power supply.
RET
Retransmission output
4-20 mA DC or
0-20 mA DC
15 V DC loop power supply
14.5-18.0 V DC
(Max. 21 mA DC)
+
-
+
-
Default: 4-20 mA DC
Default: PV
retransmission
Load resistance 600 Ω or less
Retransmission output
(Equipped as standard)
205
206
205
206
Can be used for 15 V DC loop
power supply when not used for
retransmission output.
VALV
(Suffix code: Type1=-1)
Position proportional control output
Resistance: 100 Ω to 2.5 kΩ
Feedback input
100%
0%
Relay contact output
HIGH
(direct)
LOW
(reverse)
COM
Contact rating: 250 V AC, 3A
30 V DC, 3 A
(resistance load)
101
102
103
310
311
312
-
Feedback input
Current (mA)
input
When feedback input is current
310
311
312
+
HBA
(Option code /HA)
Heater break alarm
Heater current detection input
CT1
CT2
COM
External contact output (transistor)
Transistor contact rating: 24 V DC, 50 mA
Heater break alarm-1
output
Heater break alarm-2
output
Common
310
311
312
HAL1
HAL2
COM
UP
307
308
309
(24 V AC/DC power supply: Option code /DC)
Power supply
100-240 V AC power supply
N
L
Allowable range:
100-240 V AC (+10%/-15%)
(free voltage)
50/60 Hz shared
110
111
24 V AC/DC power supply
-
+
110
111
112
112
N
L
(Suffix code: Type 1=-2)
Cooling-side control output
RET/OUT2
Current/voltage pulse output
0-20 mA DC,
4-20 mA DC,
Voltage pulse (12V)
+
-
205
206
Can not be used for retransmission output or
15 V DC loop power supply when
current/voltage pulse output is used.
Can be used for retransmission output or 15 V
DC loop power supply when control output is
not used.
Current output range can be changed.
Heating/cooling control output
Heating/cooling relay contact output
NO
Heating
-side
Cooling
-side
NO
COM
Contact rating: 240 V AC, 3 A
30 V DC, 3 A (resistance load)
101
102
103
OUT
OUT2
DI
(Equipped as standard)
Contact input
Contact rating: 12 V DC, 10 mA or more
External contact input
DI3
DI2
DI1
COM
Common
DI3
DI2
DI1
COM
+5V
+5V
+5V
No-voltage
contact
Transistor contact
UP
UP
209
210
211
212
209
210
211
212
Function can be changed.
Start of program operation when
DI1 changes from OFF to ON.
Stop of program operation when
DI2 changes from OFF to ON.
Start of local-mode operation when
DI3 changes from OFF to ON.
E1端子エリア
301-312
RS-485
SDB(+)
SDA(-)
RDB(+)
RDA(-)
SG
RS
-
485 communication
(Suffix code:
Type 2=1)
301
302
303
304
305
RS485
(Suffix code: Type 2=2)
External contact output
Transistor contact rating: 24 V DC, 50 mA
DO12
DO11
COM
Common
UT
Contact input / Contact output
External contact input
DI11
DI12
COM
Common
DI11
DI12
COM
+5V
+5V
No-voltage
contact
Transistor
contact
Contact rating: 12 V DC, 10 mA or more
Factory default: No function
Factory default: No function
Factory default: No function
Factory default: No function
UT UT
301
302
303
301
302
303
304
305
306
DI/DO
Function can be
assigned to the
terminals with no
function.
CC-Link communication (with Modbus master)
(Suffix code: Type 3=3)
FG:
Flame ground
SLD:
Shield
DG:
TX/RX signal ground
DB:
RX/TX signal
- signal
DA:
RX/TX signal
+ signal
CHK(red)
(Lit: User profile error/Adress error, Unlit: Normal)
L ERR(red)
(Lit: Communication failure(CRC error), Unlit: Normal)
L RUN(green)
(Lit: Normal, Unlit: No carrier detected/Communication timeout)
Not used
301
302
303
304
305
306
307
308
309
RS-485
RSB(+)
RSA(-)
SG
310
311
312
DB
DA
110Ω
CC-L
If the UP is located at the end of a
segment for the CC-Link
communication wiring,terminating
resistors are separately needed.
These are to be prepared by
users. (110 Ω: 1 pc.)